Restore Factory Defaults - This will clear the processor’s memory and may correct problem.
Remember to re-enter all customer settings for range and cal gas level after Restore Factory Defaults.
If problem persists, replace the Intelligent Sensor Module.
Unreadable Display
If due to excessive sunlight, install a sunshade to reduce glare.
Nothing Displayed – Transmitter not Responding
Verify condulet has no accumulated water or abnormal corrosion.
Verify required DC power is applied to correct terminals.
Swap with a known-good ITM to determine if ITM is faulty.
Faulty 4-20mA Output
If Sensor has a normal reading with no Faults displayed, and the 4-20 mA signal output is 0mA….
Check that wiring is properly connected at terminal blocks and through to controller inputs.
The 4-20mA output loop must be closed to avoid a Loop Fault. If the 4-20mA output is not being
used the green wire from the sensor must be connected to the (-) terminal on the Transient Protection
Module to ensure that it does not create a 4-20mA Fault. (section 2.6 Field Wiring)
Perform a “Signal Output Check” sequence via Section 3.5.8 and verify 4-20mA output with Current
Meter.
Swap with new ITM to determine if the ITM’s 4-20mA output circuit is faulty.
If the 4-20mA current loop is still out of tolerance, contact Detcon at
, or contact
Detcon customer service.
No Communication - RS-485 Modbus™
If unit has a normal reading with no Faults displayed and the Modbus™ is not communicating….
Verify that the correct (and non-duplicated) serial address is entered (per Section 3.5.6).
Check that wiring is properly connected at terminal blocks and through to controller inputs.
Perform a “Signal Output Check” sequence via Section 3.5.8 and troubleshoot wiring.
Swap with new ITM to determine if the ITM’s serial output circuit is faulty.