Time print, Do nothing (hardware print request), System info print – AW Gear Meters FEM-03 User Manual
Page 33: Single print, Fem-03 flow monitor

FEM-03 Flow Monitor
Operation and Programming Manual
32
TIME PRINT
The FEM-03 prints the following:
the current elapsed time since power-on
a sequential printout number
Rate A
PL
Rate B
PL
Job TOTAL A
Job TOTAL B
These print at a specified time interval in Hours. Valid numbers are 00.001 Hours (3.6 seconds) to 10.000
Hours. TIME PRINT reverts to a disabled state whenever power to the FEM is removed, and must be
reactivated after each power cycle.
DO NOTHING (hardware print request)
In this mode, the FEM-03 will “do nothing” until the hardware input is recognized. The FEM-03 RS232
Receive input is used to request a printout. When this mode activates, each momentary connection of
the FEM-03 RS232 RX input (terminal DN 5) to 15VDC (terminal DN 1) causes the FEM-03 to print:
the current elapsed time since power-on
a sequential printout number
Rate A
PL
Rate B
PL
Job TOTAL A
Job TOTAL B
Once this or any PRINTER function is active, the hardware print request input is also active and remains
active (even when power is reapplied to the FEM-03) until the user deactivates the PRINTER from the
programming screen.
SYSTEM INFO PRINT
Initiates a printout of all the programmed values contained in the FEM-03, providing up to 46 pieces of
information, depending on model.
SINGLE PRINT
This mode initiates a single printout of:
the current elapsed time since power-on
a sequential printout number
Rate A
PL
Rate B
PL
Job TOTAL A