Ap9604sr power considerations, Determining power requirements: table 3, Ap9604sr power considerations 19 – APC SMARTSLOT DP300E User Manual
Page 25: Determining power requirements 19, Continued, Powering the silcon triple chassis

19
Powering the Silcon Triple Chassis
AP9604SR
power
considerations
The AP9604SR model receives its power from the UPS
through the supplied 24 VDC universal adapter. The total
current required by your accessories must not exceed the
850 mA limit of the power adapter.
See “Determining power requirements: Table 3” on this
page.
To determine the total amount of current required by your
accessories, add the individual current requirements for
each SmartSlot accessory to be installed in the Silcon Triple
Chassis to the current requirements of the chassis itself.
Refer to this table.
Continued on next page
Part #
Accessory
Draw
(mA)
AP9207
Share-UPS UPS interface expander
65
AP9600
Expansion Chassis
30
AP9604
Triple Chassis
20
AP9604S[R]
Silcon Triple Chassis
90
AP9606
Web/SNMP Management Card
110
AP9607
Interface Expander
45
AP9608
Call-UPSII
35
AP9612
Measure-UPSII
60
AP9825i
Isolated Extension Cable
50
AP9830
Remote Power-Off Device
35
Table 3: Determining power requirements