beautypg.com

Step 2, Step 5, Status led – Hired-Hand HH Software: 900SS Wireless Network User Manual

Page 6: 12v gnd shield local network

background image

Part No. 4801-2995

900SS Wireless Network 4

6.2 Installing Control Side of Wireless HH.Net

Step 1. It is recommended to use the Wireless Tuning
Software with a PDA to ensure that you have the best signal at
a particular mounting point. See Section 7.

Step 2.

Mount the 900SS Module where it has the best line of

site to the 900SS module on the computer side. Use
appropriate mounting hardware for wood, masonry or other
material.

Step 3. Run twisted pair wire from 900SS Module to the first
control. If the Evolution control is on the network, connect to
it first. The power supply and HH.Net wires can be in the same
jacket.

Step 4. Wire the HH.Net connection from the 900SS Module
to the control as shown to the right.

Step 5.

Connect the other controls in parallel as shown below.















Step 6. Wire Power supply connection to 900SS.
Power supply and HH.Net cables can be run in the
same jacket.

A. If connecting to a Farm Hand Alarm or an

Evolution Controller, the power supply can be
connected directly to the control. See diagram at
right.


B. If you are not connecting to an Evolution or

Farm Hand Alarm or the 900SS is further than 30
feet, use an external power supply, HHI Part
Number 1902-2993. See diagram shown in
Section 6.1.

C. After all connection are made, if Farm Manager

is running on PC side, check the LED on the
900SS Radio. If the controller is
communicating, you should see the Status LED
flash orange. See Section 8.1 for further details.




900SS to Control

Network Connection.

Close

Aux.

+12V

+12V

Com.

Auxilliary Inputs

Relay Control

Tunnel Aux. Input Vent Aux. Input

Relay Control

Variable Module

HHNet Termination

Power Ventilation Module

Natural Ventilation Module

Var #1

Var #2

Open

U1

Open

U1

Open

U2

Open

U2

Open
AUX

Close

AUX

Open

AUX Com

Close

AUX

Com

Com.

Close

Aux.

Close

U1

Close

U1

Close

U2

Close

U2

+

+

-

-

+12V

GND Shield

Local Network

-

Sensor #1

Te

m

per

at

ur

e

S

en

so

rs

Te

m

per

at

ur

e S

en

sor

s

Black

Black

Black

Black

Black

Black

Black

Black

Black

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

Sensor #2 Sensor #3 Sensor #4 Sensor #5 Sensor #6 Sensor #7 Sensor #8

Outside

N.C.

IN

N.C.
OUT

N.O.

IN

N.O.

OUT

Auxilliary Alarm

DC Power Supply

+12V +5V

115 V

230 V

AC Supply

L1

L2

Evolution Control

900SS

The Diagram shown is for the Evolution Control all of the PC

compatible Farm Hands will connect the same way.

DAT

A

+

-

GN

D

HI

LO

HH NET

GN

D

HI

LO

HH NET

GN

D

HI

LO

HH NET

+

-

Terminating
Resistor

*Note: A 120 ohm terminating resistor must
be placed across the network, as shown on
the last controller on the network wire.

*Note: Twisted pair wire
can extend up to 4000 ft.

Close

Aux.

+12V

+12V

Com.

Auxilliary Inputs

Relay Control

Tunnel Aux. Input Vent Aux. Input

Relay Control

Variable Module

HHNet Termination

Power Ventilation Module

Natural Ventilation Module

Var #1

Var #2

Open

U1

Open

U1

Open

U2

Open

U2

Open

AUX

Close

AUX

Open

AUX Com

Close

AUX

Com

Com.

Close

Aux.

Close

U1

Close

U1

Close

U2

Close

U2

+

+

-

-

+12V

GND Shield

Local Network

-

Sensor #1

Te

m

per

at

ur

e

S

ens

or

s

Te

m

per

atur

e Se
nso
rs

Black

Black

Black

Black

Black

Black

Black

Black

Black

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

White

Shield

Sensor #2 Sensor #3 Sensor #4 Sensor #5 Sensor #6 Sensor #7 Sensor #8

O utside

N.C.

IN

N.C.
OUT

N.O.

IN

N.O.

OUT

Auxilliary Alarm

DC Power Supply

+12V +5V

11

5 V

23

0 V

AC Supply

L1

L2

Evolution Control

900SS

+12V

+5V

DC Power Supply

Status LED