5

PERFORMANCE DATA

Table 2

Input

Output

MAX

MIN MIN

Temp.

Rise

PD MAX

Temp

Rise

PD

Unit

MBH MBH MBH CFM °F in.

of

WC

CFM

°F in.

of

WC

Size

(kW) (kW) (kW)

(cu.

m/s)

(°C) (kPa)

(cu.

m/s)

(°C) (kPa)

100

100 50 80 822 90 0.10 3,700 20 2.03

(29.3) (14.6) (23.4) (0.388) (50) (0.02) (1.746) (11) (0.51)

125

125 62.5 100 1,028 90 0.09 4,625 20 1.92

(36.6) (18.3) (29.3) (0.485) (50) (0.02) (2.183) (11) (0.48)

150

150 75 120

1,233 90 0.09 5,550 20 1.81

(43.9) (22.0) (35.1) (0.582) (50) (0.02) (2.620) (11) (0.45)

175

175 87.5 140 1,439 90 0.09 6,475 20 1.86

(51.2) (25.6) (41.0) (0.679) (50) (0.02) (3.056) (11) (0.46)

200

200 100 160 1,645 90 0.09 7,401 20 1.90

(58.6) (29.3) (46.9) (0.776) (50) (0.02) (3.493) (11) (0.47)

225

225 112.5 180 1,850 90

0.09 8,326 20 1.93

(65.9) (32.9) (52.7) (0.873) (50) (0.02) (3.930) (11) (0.48)

250

250 125 200 2,056 90 0.09 9,251 20 1.96

(73.2) (36.6) (58.6) (0.970) (50) (0.02) (4.366) (11) (0.49)

300

300 150 240 2,467 90 0.10 11,101 20 2.00

(87.8) (43.9) (70.3) (1.164) (50) (0.02) (5.240) (11) (0.50)

350

350 175 280 2,878 90 0.10 12,951 20 2.02

(102.5) (51.2) (82.0) (1.358) (50)

(0.02) (6.113) (11) (0.50)

400

400 200 320 3,289 90 0.10 14,801 20 2.05

(117.1) (58.6) (93.7) (1.552) (50)

(0.02) (6.986) (11) (0.51)

NOTE:
Ratings are shown for elevations up to 2,000 feet (610M) above sea level. Above 2,000 feet (610M), input must be derated 4% for
each 1,000 feet (305M) above sea level. When units are installed in Canada, any reference to derations at altitudes in excess of 2,000
feet (610M) are to be ignored. At altitudes of 2,000 to 4,500 feet (610 to 1372M), the units must be orificed to 90% of the normal
altitude rating, and be so marked in accordance with the ETL certifi cation.