beautypg.com

Sterling QVSD User Manual

Page 19

background image

19

Table 8 - Main Burner Orifi ce Schedule*

PILOT ADJUSTMENT
1. Remove the PILOT ADJUSTMENT CAP.
2. Adjust the pilot screw to provide a properly sized

fl ame.

3. A proper fl ame is a soft, steady fl ame that envelops

3/8 to 1/2 inches (9.5 to 12.7mm) of the fl ame sensor.

4. Replace the pilot adjustment cap.

MANIFOLD PRESSURE ADJUSTMENT
If the manifold pressure requires adjustment, remove
the cap from the pressure regulator and turn the
adjustment screw clockwise to increase the pressure,
and counterclockwise to decrease the pressure. The
adjusted manifold pressure should not vary more
than 10% from the pressures specifi ed in Table 8.

* This schedule is for units operating at normal altitudes of 2000 feet (610m)
or less. Special orifi ces are required for installations above 2000 feet (610m).

When installed in Canada, any references to deration at altitudes in excess of
2000 feet (610m) are to be ignored. At altitudes of 2000 to 4500 feet (610 to
1372m), the unit heaters must be orifi ced to 90% of the normal altitude rating,
and be so marked in accordance with the ETL certifi cation.

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

*

INPUT

IN

1000

BTU

NO. OF

BURNER

ORIFICES

3.5 Inch WC

(0.9 kPa)

1

0.5 Inch WC

(2.6 kPa)

MANIFOLD

PRESSURE

PROPANE

TYPE OF GAS

NATURAL

2500 BTU/Ft

3

(93.1 MJ/m

3

)

1075 BTU/Ft

3

(40.1 MJ/m

3

)

HEATING

VALUE

100

125

150

175

200

225

250

300

350

400

4

5

6

7

8

9

10

12

14

16

96
42

120

42

140

42

163

42

186

42

210

42

233

42

280

42

326

42

372

42

40
54
50
54
60
54
70
54
80
54
90
54

100

54

120

54

140

54

160

54

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

FT

3

/HR

ORIFICE DRILL

GAS INPUT RATE

Never overfi re the duct furnace, as this

may cause unsatisfactory operation, or shorten the
life of the heater.

Check the gas input rate as follows (Refer to General
Safety Information section for metric conversions).

1. Turn off all gas appliances that use gas through the

same meter as the unit heater.

2. Turn the gas on to the unit heater.
3. Clock the time in seconds required to burn 1 cubic ft.

of gas by checking the gas meter.

4. Insert the time required to burn one cubic foot of gas

into the following formula and compute the input rate

3600 (Sec. per Hr.) x BTU/Cu./Ft.

= Input Rate

Time (Sec.)

For example, assume the BTU content of one cubic foot
of gas is 1000, and that it takes 18 seconds to burn one
cubic foot of gas.
3600 x 1000

= 200,000
18

NOTICE: If the computation exceeds, or is less than
95% of the gas BTU/hr. input rating (see Table 2),
adjust the gas pressure.

Adjust the gas pressure as follows:
1. NATURAL GAS: Best results are obtained when

the duct furnace is operating at its full rated input
with the manifold pressure of 3.5 inch WC (0.9 kPa).
Adjustment of the pressure regulator is not normally
necessary since it is preset at the factory. However,
fi eld adjustment may be made as follows:

a. Attach manometer at the pressure tap

plug below the control outlet.

b. Remove the regulator adjustment screw cap,

located on the combination gas valve.

c. With a small screwdriver, rotate the adjustment

screw clockwise to increase pressure.

d. Replace regulator adjustment screw cap.

2. PROPANE GAS: An exact manifold pressure of 10.0

inch WC (2.5 kPa) must be maintained for proper
operation of the duct furnace. If the unit is equipped
with a pressure regulator on the combination gas
valve, follow steps “a” through “d” above. If the unit is
not so equipped, the propane gas supply system
pressure must be regulated to attain this manifold
operating pressure.

This manual is related to the following products: