INSTALLATION (Continued)

Vent Systems

Termination Clearance Requirements

Structure/Object

Minimum Clearance

for Termination Locations

USA

CANADA

Door, window, or gravity vent
inlet; combustion air inlet for
other appliances

9 inches for 10,000
to 50,000 BTU/Hr
input; 12 inches for
input exceeding
50,000 BTU/Hr.

9 inches (230mm)
for 10,000 to
50,000 BTU/Hr
input; 12 inches
(305mm) for input
exceeding 50,000
BTU/Hr.

Forced air inlet within 10 feet

3 feet above

6 feet (1.8m)

Adjoining Building or parapet

10 feet

10 feet (3.04m)

Adjacent public walkways

7 feet above
grade

7 feet (2.1m) above
grade

Electric, gas meters
& regulators

4 feet horizontal

3 feet (0.9m)
horizontally from
meter/regulator
asembly. 6 feet
(1.8m), any
direction, from
a gas service
regulator vent
outlet

Above grade level*

1 feet

1 feet (0.3m)

*Minimum above maximum snow depth, or per local code, whichever is
greater.