17

PIPE INSTALLATION

1. Install the gas piping in accordance with applicable

local codes.

2. Check gas supply pressure. Each duct furnace must

be connected to a manifold pressure and a gas
supply capable of supplying its full rated capacity as
specifi ed in Table 7. A fi eld LP tank regulator must
be used to limit the supply pressure to a maximum
of 14 inches WC (3.5 kPa). All piping should be sized
in accordance with the latest edition of ANSI
Standard Z223.1 (NFPA 54), National Fuel Gas
Code; in Canada, according to CSA B149. See
Tables 1, 6 & 7 (of this manual) for correct gas piping
size. If gas pressure is excessive on natural gas
applications, install a pressure regulating valve in the
line upstream from the main shutoff valve.

3. Adequately support the piping to prevent strain on

the gas manifold and controls.

4. To prevent the mixing of moisture with gas, run the

take-off piping from the top, or side, of the main.

5. Duct furnaces are shipped with a combination valve

which includes:

a. Manual "A" valve

b. Manual "B" valve

c.

Solenoid

valve

d.

Pilot

safety

e.

Pressure

regulator

Pipe directly into the combination valve (see Figure
10).

6. A 1/8 inch N.P.T. plugged tapping, accessible for test

gauge connection, must be installed immediately
upstream of the gas supply connection to the
appliance.

7. Provide a drip leg in the gas piping near the gas duct

furnace. A ground joint union and a manual gas
shutoff valve should be installed ahead of the unit
heater controls to permit servicing. The manual
shutoff valve must be located external to the jacket
(See Figure 10).

8. Make cer tain that all connections have been

adequately doped and tightened.

Do not over tighten the inlet gas piping

into the valve. This may cause stresses that will crack
the valve!

D3631C

NOTICE: Use pipe joint sealant resistant to the action
of liquefied petroleum gases regardless of gas
conducted.

Check all pipe joints for leakage

using a soap solution or other approved method.
Never use an open fl ame or severe personal injury
or death may occur!

Figure 10- Pipe Installation, Standard Controls

Never use an open fl ame to detect

gas leaks. Explosive conditions may exist which
will result in personal injury or death.

The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system in excess of 1/2 psig
(3.5 kPa).

The appliance must be isolated from the gas supply piping
system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psig
(3.5 kPa).