PIPE INSTALLATION

(Continued)

Table 7 - Gas Supply Pressure Requirements

Heating Value

Natural Gas

Propane Gas

1075 Btu/Ft

3

2500

Btu/Ft

3

(40.1 MJ/m

3

) (93.1

MJ/m

3

)

Manifold Pressure

Single Stage Application

3.5 in. WC

10.0 in. WC

(0.87 kPa)

(2.49 kPa)

Two Stage Application - High Fire

3.5 in. WC

10.0 in. WC

(0.87 kPa)

(2.49 kPa)

Two Stage Application - Low Fire

1.1 in. WC

3.8 in. WC

(0.27 kPa)

(0.95 kPa)

Modulating Application - High Fire

3.5 in. WC

10.0 in. WC

(0.87 kPa)

(2.49 kPa)

Modulating Application - Low Fire

0.9 in. WC

3.5 in. WC

(0.22 kPa)

(0.87 kPa)

Minimum Supply Pressure

Single Stage Application

5.0 in. WC

11.0 in. WC

(1.24 kPa)

(2.74 kPa)

Two Stage Application

6.5 in. WC

11.5 in. WC

(1.62 kPa)

(2.86 kPa)

Modulating Application

6.5 in. WC

11.5 in. WC

(1.62 kPa)

(2.86 kPa)

Maximum Supply Pressure

14.0 in. WC

14.0 in. WC

(3.49 kPa)

(3.49 kPa)