Table 9 - Troubleshooting Guide

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

1. Loose

wiring.

2. Defective motor overload

protector or defective motor.

3. Defective power ventor relay.

1. Fan relay heater element

improperly

wired.

2. Defective ventor relay switch.
3. Motor protector cycling on and off.

4. Motor not properly oiled.

1. Improperly wired ventor relay.
2. Main burners not lighting while

thermostat calls for heat.

3. Defective ventor relay.

1. Incorrect gas input.
2. Heater

undersized.

3. Thermostat

malfunction.

4. Heater cycling on high limit.

5. Check outside dampers if used.

1. Thermostat

malfunction.

2. Heater runs continuously.

1. Fan relay heater element

improperly

wired.

1. Check and tighten all wiring

connections per diagrams.

Thermostat wires tagged “W” and

“G” must be connected together

(unless special thermostats are

used; if so, see thermostat wiring

diagram). See “Electrical

Connections”.
2. Replace

motor.

3. Check 24V across 1 and 3

terminals on fan relay. If 24V is

present, jumper terminals

numbered 2 and 4. If motor runs,

the relay is defective and must be

replaced. If 24V in not present,

check wiring per wiring diagrams.

1. Be sure ventor relay heater

terminals are connected per

diagrams.
2. Replace ventor motor.
3. Check motor amps against motor

name plate rating, check voltage,

replace power ventor motor if

defective.
4. Refer to label on motor.

1. Check all wiring.
2. Refer to H & N Symptoms.

3. Replace ventor relay.

1. Refer

to

“Operation”.

2. This is especially true when

heated space is enlarged. Have

heat loss calculated and compare

to heater output (80% of input).

Your gas supplier or installer can

furnish this information. If heater is

undersized, add additional heaters.

3. Replace

thermostat.

4. Check air movement through heat

exchanger. Check voltage to fan

motor. Clean power ventor motor.

5. Adjust dampers accordingly.

1. Replace

thermostat.

2. Check wiring diagrams; Check

operation at valve. Look for short

(such as staples piercing thermo-

stat wiring) and correct: Replace

gas valve; Refer to “Operation”.

1. Be sure fan relay heater terminal

are connected per diagrams.

O. Power ventor will not run.

P. Power ventor motor turns

on and off while burners

are

operating.

Q. Power ventor motor will

not

stop.

R. Not enough heat.

T. Too much heat.

U. Cold air is delivered on

start-up