1. Pressure regulator set too high.

2. Defective

regulator.

3. Burner orifi ce too large.

1. Excessive primary air.

2. Burner orifi ce too small.

1. Too much primary air.
2. Noisy

pilot.

3. Irregular orifi ce causing whistle or
resonance.
4. Excessive gas input.

1. Insuffi cient primary air.

2. Clogged burner ports.
3. Misaligned

orifi

ces.

4. Clogged draft hood.
5. Air

shutter.

6. Insuffi cient combustion air.

1. Blocked

Venting.

2. Insuffi cient combustion air.

3. Blocked heat exchanger
4. Air leak into combustion chamber

or draft hood.

1. Shut off gas immediately.

2. Blocked heat exchanger/venting.
3. Drafts around heater.

4. Negative pressure in building.
5. Blocked draft hood.

1. Reset manifold Pressure. Refer to
“Operation”.
2. Replace regulator section of

combination gas valve or

complete

valve.

3. Check with local gas supplier for

proper orifi ce size, and

replace. Refer to “Operation”.

1. Close air shutter. Refer to

“Operation”.
2. Check with local gas supplier for

proper orifi ce size and replace.

Refer

to

“Operation”.

1. Close air shutter.
2. Reduce pilot gas. Refer to

“Operation”.
3. Replace

orifi

ce.

4. Reset manifold pressure. Refer to

“Operation”: Replace regulator

section of combination gas valve

or complete valve; or Check with

local gas supplier for proper orifi ce

size, and replace. Refer to

“Operation”.

1. Open air shutter. Refer to

“Operation”.
2. Clean main burner ports.
3. Replace manifold assembly.
4. Clean draft hood.
5. Check for dust or lint at air mixer

opening and around air shutter.

6. Check for obstruction in

combustion air inlet cap

and piping. See “Installation”.


1. Clean fl ue. Refer to “Installation”.
2. Check for obstruction in

combustion air inlet cap

and piping. See “Installation”.

3. Clean

heater.

4. Determine cause and repair

accordingly.

1. Inspect all gas piping and
repair.
2. Clean heat exchanger/fl ue.
3. Eliminate drafts. Refer to

“Installation”.
4. See

“Installation”.

5. Clean draft hood.

Table 9 - Troubleshooting Guide

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

A. Flame lifting from
burner

ports.

B. Flame pops back.

C. Noisy

fl

ame.

D. Yellow tip fl ame (some

yellow tipping on propane

gas is permissible).

E. Floating

fl

ame.

F. Gas odor.

This manual is related to the following products: