beautypg.com

Sterling TD User Manual

Page 33

background image

33

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

N. High limit is tripping.


O. Power ventor will not run.




P. Power ventor turns on

and off during operation.



Q. Power ventor will not stop.

R. Noisy power ventor.


1. Unit is over fi red.

2. Incorrect

airfl

ow.

3. Defective high limit switch.

4. Defective control board.

1. No power supply to the unit.

2. Thermostat not calling.

3. Loose wiring or connection.

4. Motor overload protection is tripping

or bad motor.

5. Defective control board.

6. Motor not oiled.

1. Power ventor improperly wired.

2. Motor overload cycling or defective
motor.

3. Defective control board.

4. Motor not oiled.

1. Power ventor improperly wired.

2. Main burner did not light on call for

heat.
3. Defective control board.

1. Power ventor wheel loose.
2. Power ventor wheel is dirty.
3. Power ventor wheel is rubbing on
housing.
4. Bearings are dry.

1. Refer to “Gas Input Rate” in the

Operation section of this manual.

Check orifi ce size. Replace if too large.

2. See blower manufacturer for
corrective

action(s).

3. Check operation of switch. If switch is

open during operation, check gas

pressure and/or CFM; adjust

accordingly. If switch is open during

start-up, replace switch.

4. Check for 24V on line side of high

limit. Constant voltage should be

recorded. If not, control board is

suspect. Check fl ash code.

1. Turn on power supply, check fuses

and replace if bad.

2. Turn up thermostat. Check for 24V on

terminals R and W1 on terminal strip.

3. Check all wiring in the power vent

circuit to ensure good connection,

including

“neutral.”

4. Check for 115V between motor leads

and check amp draw of motor.

Replace if necessary.

5. Check for continuous 115V on

terminal “CBM Blower” and neutral

during call for heat. If not present and

all checks are normal, replace.

6. Refer to “Maintenance” section of this
manual.
1. Check power ventor circuit per wiring
diagram.
2. Check motor voltage and amp draw

against motor name plate, replace if

motor found defective.

3. Check for continuous 115V on

terminal “CBM Blower” and neutral

during call for heat. If not present

and all checks are normal, replace.

4. Refer to “Maintenance” section of this
manual.
1. Check power ventor circuit per wiring
diagram.
2. Heater is in lockout mode; check fl ash

code table for problem.

3. If no fl ash codes present along with

no call for heat, replace control board.

1. Replace or tighten.
2. Clean power ventor wheel.
3. Realign power ventor wheel.

4. Oil bearing on power ventor motor

(refer to label on motor).

Table 8A – Tubular Duct Furnace Troubleshooting Guide (continued)