Venting (continued) – Sterling TD User Manual

Page 19

background image

19

Figure 8A - Vertically Vented Category III, Standard Combustion

VENTING (continued)

Figure 8B - Horizontally Vented Category III, Standard Combustion

D9379B

D9378B

Condensate Drain with Trap
(if requried by local authorites)

Approved Vent

Terminal

5 ft (1.52 m) Min

1FT (305 mm) Min. above grade
plus max. snow depth, or per
local code, whichever is greater.

1 FT. Min
(305 mm)

1/4" per foot Min. Slope
(21mm/m)

2 ft Min.

(0.61 m Min)

5 ft. Min.

(1.52 m Min.)

6" (152 mm) Min.

Distance from pipe

to ceiling

10 ft. Max. (3.05 m)
(Not to Exceed 75%
Vertical Flue Height)

1/4" per foot Min. Slope
(21 mm/m)

Thimble

Roof

Use Insulated Stack Outdoors

Approved Vent Terminal