OPERATION (continued)

Table 7A

High Altitude Deration - United States

Altitude

Manifold Pressure

BTU Output

1

Natural Gas

2

Liquid Propane

3

Feet

Meters

Inches W.C.

Pa

Inches W.C.

Pa

Percentage

0-2,000

0-610

3.5

872

10.0

2491

100%

2,001-3,000

611-915

3.2

797

9.2

2292

96%

3,001-4,000

916-1220

2.9

722

8.4

2092

92%

4,001-5,000

1221-1525

2.7

673

7.7

1918

88%

5,001-6,000

1526-1830

2.4

598

7.0

1744

84%

6,001-7,000

1831-2135

2.2

548

6.4

1594

80%

7001-8000

2136-2440

2.0

498

5.7

1420

76%

8001-9000

2441-2745

1.8

448

5.1

1270

72%

9001-10,000

2746-3045

1.6

399

4.6

1145

68%

Notes: 1. Deration based on ANSI Z223.1 (NFPA 54).

2. Table based on heating value of 1,050 BTU/Cu. feet at sea level.

3. Table based on heating value of 2,500 BTU/Cu. feet at sea level.

4. Consult local utility for actual heating value.

High Altitude Deration - Canada

Altitude

Manifold Pressure

BTU Output

1

Natural Gas

2

Liquid Propane

3

Feet

Meters

Inches W.C.

Pa

Inches W.C.

Pa

Percentage

0-2,000

0-610

3.5

872

10.0

2491

100%

2001-3000

611-915

3.2

797

9.2

2292

96%

3001-4000

916-1220

2.9

722

8.4

2092

92%

4001-4500

1221-1371

2.8

697

7.9

1968

90%

Notes: 1. Deration based on CGA 2.17-M91

2. Table based on heating value of 1,050 BTU/Cu. feet at sea level.

3. Table based on heating value of 2,500 BTU/Cu. feet at sea level.

4. Consult local utility for actual heating value.