beautypg.com

Troubleshooting – Watlow Series L Temperature Limit User Manual

Page 13

background image

Wa t l ow S e r i e s L

• 11 • C h a p te r

5 :

Tro u bl e s h o o t i n g

Indication

Probable Cause(s)

Corrective Action

On indicating limits, the dis-
play is not illuminated.

• Power supply switch off.
• Fuse blown.
• Breaker tripped.
• Safety interlock door switch activated.
• Wiring incorrect or open.
• Power supply voltage incorrect.
• Defective limit.

• Turn switch on.
• Replace fuse (check cause of failure).
• Reset breaker (check cause of failure).
• Close door.
• Check wiring.
• Verify input power
• Repair or replace limit.

Troubleshooting thermocouple inputs

Temperature reading is incor-
rect, showing a sensor error,
[Er;In] , or ALARM LED is
switching at the wrong tem-
perature.

• Setting for degree C or F is incorrect. • Check the model part number for

Degree C or F. If the model has Incre-
ment/Decrement keys, then the C/F
setting is adjustable.

• Sensor or limit may be bad. Sensor

connections may be bad.

• Place a jumper wire across the ther-

mocouple input terminals. The display
should indicate ambient temperature.
If it does, the limit is OK.

- For high limit: Start with limit set

point above ambient temperature,
ALARM LED should be off. Decrease
limit set point until ALARM LED goes
on. It should be approximately ambi-
ent temperature.

- For low limit: Start with limit set point

below ambient temperature, ALARM
LED should be off. Increase limit set
point until ALARM LED goes on. It
should be approximately ambient tem-
perature.

• Ambient temperature in the control

cabinet is over 70°C.

• Measure temperature in cabinet to

ensure it is below 70C. Vent cabinet or
add fans if necessary.

• Ground loop problem. Can occur when

using a switched DC output and a
grounded thermocouple.

• Remove power from the system. Use

an ohm meter to measure resistance
between output DC- and the thermo-
couple sheath. If there is continuity,
replace sensor with an ungrounded
thermocouple.

Temperature seems to be de-
creasing, but actual process is
increasing.

• Thermocouple polarity is reversed. In

the US, red wire insulation denotes
the negative wire.

• Check thermocouple connections. All

connections, including extension wire
must maintain the correct polarity.
Correct polarity problems.

Temperature seems to be read-
ing low and not increasing
while actual process tempera-
ture is increasing.

• Sensor is bad. Thermocouple is shorted. • Check thermocouple connections.

Check thermocouple wire insulation
to make sure it is not damaged, caus-
ing the wires to short (making a new
junction).

Temperature seems to be off-
set from actual process tem-
perature, or the ALARM LED
switches on at the wrong tem-
perature. The offset changes
with changes in process tem-
perature.

• Copper wire was used instead of ther-

mocouple extension wire. Connectors
of metals different than thermocouple
metal were used to splice or make
connections.

• Check thermocouple connections.

Check to make sure that only thermo-
couple extension wire of the correct
type was used to extend thermocouple
leads. Replace if necessary.

Troubleshooting