Series 93 model number information, Ordering information, Appendix – Watlow Series 93 User Manual
Page 45
Ordering Information
(2219)
93 _ _ - 1 _ _ _ - 0 0_ _
Part Number
Microprocessor-based
1/16 DIN, Single Input, Dual Output,
Two-, Four-Digit Displays
IP65/NEMA 4X
1
Option
A = Without IP65/NEMA 4X Rating
B = With IP65/NEMA 4X Rating
CE Option
A = Without CE
B = With CE
Output 1
C = Switched dc output, non-isolated
D = Electromechanical relay, Form C, 5A,
without contact suppression
2, 3
F = Process, 4-20mA (dc), non-isolated
K = Solid-state relay, Form A, 0.5A, without
contact suppression
3
Output 2
A = None
C = Switched dc output, non-isolated
D = Electromechanical relay, Form C, 5A,
without contact suppression
2, 3
K = Solid-state relay, Form A, 0.5A,
without contact suppression
3
Line Voltage/Power
0 = 100 to 240V~ (ac) nominal (high voltage)
1 = 12 to 24Vı (ac/dc) (low voltage)
X = Custom Parameters
Display
Upper/Lower
RR =
Red/Red
RG =
Red/Green
GR =
Green/Red
GG =
Green/Green
XX = Custom Overlay
1
To effect IP65/NEMA 4X rating requires a minimum mounting panel thickness of 1.5 mm (0.06 inch)
and surface finish not rougher than 812 µ mm (0.32µ inch). Use Greenlee punch #60287.
2
Electromechanical relays warranted for 100,000 closures only. Solid-state switching devices recom-
mended for applications requiring fast cycle times or extended service life.
3
Switching inductive loads (relay coils, etc.) requires using an RC suppressor. Quencharc from ITW
PAKTRON is recommended, Watlow part number 0804-0147-0000.
W a t l o w S e r i e s 9 3
A p p e n d i x
■
A . 1 3
Appendix
Series 93 Model Number Information