Operation menu table, Operation menu prompts and descriptions, Ahi} {`aut} {`cal – Watlow Series 93 User Manual
Page 25: Setup, Operation menu
W a t l o w S e r i e s 9 3
S e t u p
■
4 . 7
Setup
Operation Parameters
Value
Range
Factory Default
[`Pb1]
If
[`dFL] is set to [``US]:
0 to 555°C/0 to 999°F/0 to 999 Units
25°F
0 to 55.5°C/0 to 99.9°F/0 to 99.9 Units
2.5°F
0 is control.
[`HSC] is set to switch differential
If
[`dFL] is set to [``SI]:
0.0 to 999.9% of span
3%
[`rE1]
0.00 to 9.99 repeats/minute
0.00 repeats/minute
0.00 = No Reset. Won't appear if
[`Pb1] is set to 0
or
[`dFL] is set to [``SI].
[`It1]
0.0 to 99.9 minutes/repeat. 0.00 = No Integral.
00.0 minutes/repeat
Won't appear if
[`Pb1] is set to 0 or [`dFL] is set to [``US].
[`rA1]
0.00 to 9.99 minutes
0.00 minutes
0.00 = No Rate. Will not appear if
[`Pb1] is set to 0
or
[`dFL] is set to [``SI].
[`dE1]
0.00 to 9.99 minutes. 0.00 = No Derivative.
0.00 minutes
Won't appear if
[`Pb1] is set to 0 or [`dFL] is set to [``US].
[`Ct1]
0.1 to 999.9
5.0 seconds
Won't appear if
[`Pb1] is set to 0, or [`420].
[`Pb2]
Same as
[`Pb1]. [`Pb2] lower limit = 1, 0.1, 0.01
[`rE2]
Same range as
[`rE1].
[`It2]
Same range as
[`It1].
[`rA2]
Same range as
[`rA1].
[`dE2]
Same range as
[`dE1].
[`Ct2]
Same range as
[`Ct1].
[`ALO] Deviation [``dE]
-999 to 0
-999
Process
[``Pr]
[``rL] to [`AHI]
[``rL]
Will not appear if
[`Ot2] is set to [``no] or [`Con].
[`AHI] Deviation [``dE]
0 to 999
999
Process
[``Pr]
[`ALO] to [``rH]
[``rH]
Will not appear if
[`Ot2] is set to [``no] or [`Con].
[`CAL]
±100°C/±180°F/±180 Units
0
[`AUt]
0 to 3
0
If a mechanical relay or contactor is switching power to the load, a longer
cycle time may be desirable to minimize wear on the mechanical compo-
nents. Typical life of a mechanical relay is 100,000 cycles.
Range: 0.1 to 999.9 seconds
Default: 5.0 seconds
Alarm Low: Represents the low process alarm or low deviation alarm. This para-
meter will not appear if
[`Ot2] is set to no or [`Con].
Range if
[`Ot2] is set to [`dEA] or [``dE]: -999 to 0
Default: -999
Range if
[`Ot2] is set to [`PrA] or [``Pr]: [``rL] to [`AHI] Default: [``rL]
Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if
[`Ot2] is set to [``no] or [`Con].
Range if
[`Ot2] is set to [`dEA] or [``dE]: 0 to 999
Default: 999
Range if
[`Ot2] is set to [`PrA] or [``Pr]: [`ALO] to [``rH] Default: [``rH]
Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -100°C to 100°C/-180°F to 180°F/-180 units to 180 units; or
-10.0°C to 10.0°C/-18.0°F to 18.0°F
Default: 0
Autotune: Initiates an autotune.
Range: 0 is set to off, 1 is set to slow, 2 is set to medium, 3 is set to fast
Default: 0
Table 4.7 -
Operation Menu
Prompts and
Descriptions.
{`ALO}
Operation Menu
Document your Series 93 Operation Parameters in the Value column below.
Do not mark any values here; make photocopies instead.
{`AHI}
{`AUt}
{`CAL}