W a t l o w S e r i e s 9 3

S e t u p

4 . 7

Setup

Operation Parameters

Value

Range

Factory Default

[`Pb1]

If

[`dFL] is set to [``US]:

0 to 555°C/0 to 999°F/0 to 999 Units

25°F

0 to 55.5°C/0 to 99.9°F/0 to 99.9 Units

2.5°F

0 is control.

[`HSC] is set to switch differential

If

[`dFL] is set to [``SI]:

0.0 to 999.9% of span

3%

[`rE1]

0.00 to 9.99 repeats/minute

0.00 repeats/minute

0.00 = No Reset. Won't appear if

[`Pb1] is set to 0

or

[`dFL] is set to [``SI].

[`It1]

0.0 to 99.9 minutes/repeat. 0.00 = No Integral.

00.0 minutes/repeat

Won't appear if

[`Pb1] is set to 0 or [`dFL] is set to [``US].

[`rA1]

0.00 to 9.99 minutes

0.00 minutes

0.00 = No Rate. Will not appear if

[`Pb1] is set to 0

or

[`dFL] is set to [``SI].

[`dE1]

0.00 to 9.99 minutes. 0.00 = No Derivative.

0.00 minutes

Won't appear if

[`Pb1] is set to 0 or [`dFL] is set to [``US].

[`Ct1]

0.1 to 999.9

5.0 seconds

Won't appear if

[`Pb1] is set to 0, or [`420].

[`Pb2]

Same as

[`Pb1]. [`Pb2] lower limit = 1, 0.1, 0.01

[`rE2]

Same range as

[`rE1].

[`It2]

Same range as

[`It1].

[`rA2]

Same range as

[`rA1].

[`dE2]

Same range as

[`dE1].

[`Ct2]

Same range as

[`Ct1].

[`ALO] Deviation [``dE]

-999 to 0

-999

Process

[``Pr]

[``rL] to [`AHI]

[``rL]

Will not appear if

[`Ot2] is set to [``no] or [`Con].

[`AHI] Deviation [``dE]

0 to 999

999

Process

[``Pr]

[`ALO] to [``rH]

[``rH]

Will not appear if

[`Ot2] is set to [``no] or [`Con].

[`CAL]

±100°C/±180°F/±180 Units

0

[`AUt]

0 to 3

0

If a mechanical relay or contactor is switching power to the load, a longer
cycle time may be desirable to minimize wear on the mechanical compo-
nents. Typical life of a mechanical relay is 100,000 cycles.
Range:
0.1 to 999.9 seconds

Default: 5.0 seconds

Alarm Low: Represents the low process alarm or low deviation alarm. This para-
meter will not appear if

[`Ot2] is set to no or [`Con].

Range if

[`Ot2] is set to [`dEA] or [``dE]: -999 to 0

Default: -999

Range if

[`Ot2] is set to [`PrA] or [``Pr]: [``rL] to [`AHI] Default: [``rL]

Alarm High: Represents the high process alarm or high deviation alarm. This
parameter will not appear if

[`Ot2] is set to [``no] or [`Con].

Range if

[`Ot2] is set to [`dEA] or [``dE]: 0 to 999

Default: 999

Range if

[`Ot2] is set to [`PrA] or [``Pr]: [`ALO] to [``rH] Default: [``rH]

Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -100°C to 100°C/-180°F to 180°F/-180 units to 180 units; or
-10.0°C to 10.0°C/-18.0°F to 18.0°F

Default: 0

Autotune: Initiates an autotune.
Range: 0 is set to off, 1 is set to slow, 2 is set to medium, 3 is set to fast
Default: 0

Table 4.7 -
Operation Menu
Prompts and
Descriptions.

{`ALO}

Operation Menu

Document your Series 93 Operation Parameters in the Value column below.
Do not mark any values here; make photocopies instead.

{`AHI}

{`AUt}

{`CAL}