Setup menu table, Setup, Setup menu – Watlow Series 93 User Manual
Page 23
W a t l o w S e r i e s 9 3
S e t u p
■
4 . 5
Setup
Parameter
Value
Range
Factory Default
Appears If:
[
`LOC]
0 to 4
0
[``In]
[```J], [```H], [```t], [```n], [```S],
[```J]
DIP switch selectable.
[`rtd], [`r†d], [`0-5], [`420]
[`dEC]
0, 0.0, 0.00
0
[``In] is set to [`0-5] or [`420]
[`C_F]
[```C] or [```F]
Dependent on
[`dFL]
[``In] is set to [```J], [```H],
[```t],[```n],[```S], [`rtd], or
[`r†d]
[``rL]
[``rL] to [``rh]
Input dependent
[``rh]
``rh] to [``rL]
Input dependent
[`Ot1]
[``ht] or [``CL]
[``ht]
[`HSC]
1 to 55, 0.1 to 5.5, 0.01 to 0.55°C
2, 0.2, 0.02°C
1 to 99, 0.1 to 9.9, 0.01 to 0.99°F
3, 0.3, 0.03°F
[`Ot2]
[`Con] Control
[`Con]
[`PrA] Process alarm
[``Pr] Process with no alarm message
[`dEA] Deviation alarm
[``dE] Deviation with no alarm message
[``no] None
[`HSA]
1 to 5555, 0.1 to 555.5, 0.01 to 55.55°C
2, 0.2, 0.02°C
[`Ot2] is not set to [`Con] or [``no]
1 to 9999, 0.1 to 999.9, 0.01 to 99.99°F
3, 0.3, 0.03°F
[`LAt]
[`LAt] or [`nLA]
[`nLA]
[`Ot2] is not set to [`Con] or [``no]
[`SIL]
[``On] or [`OFF]
[`OFF]
[`Ot2] is set to [`dEA] or [``dE]
[`rtd]
[`JIS] or [`din]
[`din]
[``In] is set to [`rtd] or [`r†d]
[`rP`]
[`Str] Ramping on power up
[`OFF]
[``On] Ramping to set point at all times
[`OFF] None
[`rt`]
0 to 9999
100°/hr
[``rP] is not set to [`OFF]
[`P`L]
0 to 100
100
[`Ot1] or [`Ot2] is set to [``ht]
[`dsP]
[`nor] normal
[`nor]
[`SEt] Set Point (lower only)
[`Pro] Process (upper only)
Input Type
Sensor Range Low
Sensor Range High
[```J]
0°C/32°F
750°C/1382°F
[```H]
-200°C/-328°F
1250°C/2282°F
[```t]
-200°C/-328°F
350°C/662°F
[```n]
0°C/32°F
1250°C/2282°F
[```S]
0°C/32°F
1450°C/2642°F
[`rtd]
(1°)
-200°C/-328°F
700°C/1292°F
[`r†d] (0.1°)
-128.8°C/-199.9°F
537.7°C/999.9°F
[`420]
4mA/-999 units
20mA/9999 units
[`0-5]
0VÎ (dc)/-999 units
5VÎ (dc)/9999 units
Table 4.5a -
Input Ranges.
{`dSP}
Table 4.5b -
Setup Menu Prompts and
Descriptions.
Setup Menu
Power Limiting: The power limiting function in % power for heat only. Power
Limiting will function if
[`pb1] is not set to [```0].
Range: Dependent on output type. 0 to 100
Default: 100
Display: Selects which displays are active or viewable. Five seconds after select-
ed, the appropriate display goes blank. Press ‰Advance, ¿Up-arrow or ¯Down-
arrow to override this feature and cause the current value to be displayed for 5
seconds.
Range:
[`nor] Normal displays
Default:
[`nor]
[`SEt] Set Point - lower display only
[`Pro] Process - upper display only
NOTE:
Document your Setup
Menu parameters below.
Do not mark any values
here; make photocopies
instead.
[`P`L]