Specifications, Appendix – Watlow Series 93 User Manual
Page 44
A . 1 2
■
A p p e n d i x
W a t l o w S e r i e s 9 3
Appendix
Specifications (2218)
Control Mode
• Microprocessor-based, user-selectable control modes
• Single input, dual output
• 2.5Hz Input Sampling Rate
• 1Hz Display Update Rate
• Ramp to set point: 0 to 9999 degrees or units per hour
• Heat and cool autotune
Operator Interface
• Sealed membrane front panel
• Dual, four-digit red or green displays
• ‰Advance, ¿Up-arrow, ¯Down-arrow, and ˆInfinity keys
• User-selectable screen display
Accuracy
• Calibration accuracy and sensor conformity: ±0.1% of span, ±1°C
@ 25°C ± 3°C (77°F ± 5°F) ambient and rated line voltage
• Accuracy span: 540°C (1000°F) minimum
• Temperature stability: ±0.2°C/°C (±0.2°F/°F) rise in ambient maxi-
mum
Sensors/Inputs
• Thermocouple, grounded or ungrounded sensors
• RTD 2- or 3-wire, platinum, 100
Ω
@ 0°C calibration to DIN curve
(0.00385
Ω
/
Ω
/°C) or JIS curve (0.003916
Ω
/
Ω
/°C); user-selectable
• Process, 4-20mA @ 5
Ω
, or 0-5VÎ (dc) @ 10k
Ω
input impedance
• Sensor break protection de-energizes control output to protect
system or selectable bumpless transfer to manual operation
• °C or °F or process units display, user-selectable
Input Range
Specified temperature ranges represent the controller’s operation-
al span.
• Thermocouple
Type J
0
to
750°C
(32
to 1382°F)
Type K
-200
to 1250°C
(-328
to 2282°F)
Type N
0
to 1250°C
(32
to 2282°F)
Type S
0
to 1450°C
(32
to 2642°F)
Type T
-200
to
350°C
(-328
to
662°F)
• RTD Resolution (DIN or JIS)
1°
-200
to
700°C
(-328
to 1292°F)
0.1°
-128.8 to 537.7°C
(-199.9 to 999.9°F)
• Process
4-20mA @ 5
Ω
, or -999 to 9999 units
0-5V (dc) @ 10k
Ω
, or -999 to 9999 units
Output 1 (Heating or Cooling)
• Electromechanical relay
1
, Form C, 5A @ 120/240V~ (ac) maxi-
mum, without contact suppression, rated resistive load, 5A @
30VÎ (dc)
2
. Minimum contact current, 100mA @ 5VÎ (dc).
• Switched dc signal provides a non-isolated minimum turn on volt-
age of 3VÎ (dc) into a minimum 500
Ω
load; maximum on voltage
not greater than 12VÎ (dc) into an infinite load.
• 4-20mA reverse or direct acting, non-isolated 0 to 800
Ω
load.
• Solid-state relay
2
, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac)
max., opto-isolated burst fire switched, without contact suppres-
sion. Off-state output impedance is 31M
Ω
.
Output 2 (Heat, Cool or Alarm)
• Electromechanical relay
1
, Form C, 5A @ 120/240V~ (ac) maxi-
mum, without contact suppression, rated resistive load, 5A @
30VÎ (dc)
2
. Minimum contact current, 100mA @ 5VÎ (dc).
• Switched dc signal provides a non-isolated minimum turn on volt-
age of 3VÎ (dc) into a minimum 500
Ω
load; maximum on voltage
not greater than 12VÎ (dc) into an infinite load.
• Solid-state relay
2
, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac)
max., opto-isolated burst fire switched, without contact suppres-
sion. Off-state output impedance is 31M
Ω
.
• Alarm output can be latching or non-latching, and process or devi-
ation with separate high and low values. Alarm silencing (inhibit)
on power up (for deviation alarms only).
Output Configurations
• Output 1
User-selectable as: on-off: P, PI, PD, PID, heat or cool action
• Adjustable switching differential: 1 to 55°C (1 to 99°F)
• Proportional band: 0 (off) or 0 to 555°C (1 to 999°F) or 0.0 to
999.9 units
Integral: 0 (off) or 0.1 to 99.9 minutes per repeat
Reset: 0 (off) or 0.01 to 9.99 repeats per minute
Rate/derivative: 0 (off) or 0.01 to 9.99 minutes
Cycle time: 0.1 to 999.9 seconds
• Output 2
User selectable as: Control with action opposite that of Output 1
(heating or cooling)
• Process or deviation alarm with flashing alarm message
• Process or deviation alarm without alarm message
• Alarm with separate high and low set points
• Hysteresis: 1 to 9999° or units switching differential
Line Voltage/Power
• 100-240V~ (ac), -15%, +10%
4
; (85-264V~ [ac]) 50/60Hz, ±5%
• 12-24Vı (ac/dc), +10%, -15%; (10-26Vı [ac/dc]) 50/60Hz, ±5%
• Fused internally(factory replaceable only) Slo-Blo
®
type (time-lag):
1A, 250V for high voltage versions
2A, 250V for low voltage versions
• Maximum power consumption: 12VA (100 to 240V~), 7VA (12 to
24Vı)
• Data retention upon power failure via non-volatile memory
Operating Environment
3
• 0 to 65°C (32 to 149°F).
• 0 to 90% RH, non-condensing
Storage Temperature
• -40° to 85°C (-40° to 185°F)
Terminals
• #6 compression universal head screw terminals, accepts 20-14
gauge wire. Torque to 1.4 Nm (12 in-lb).
Controller Weight
• 0.2 kg (0.4 lb)
Shipping Weight
• 0.34 kg (0.75 lb)
Dimensions
• Compact 1⁄16 DIN size and IP65
4
(NEMA 4X), front panel make
the Series 93 easy to apply and maintain in a wide variety of
applications. The unique mounting bezel, gasket and collar make
installation a snap.
Overall Height:
55 mm
(2.1 inches)
Width:
55 mm
(2.1 inches)
Depth:
120 mm
(4.7 inches)
Bezel Height:
55 mm
(2.1 inches)
Width:
55 mm
(2.1 inches)
Depth:
15 mm
(0.6 inches)
Chassis Height:
45 mm
(1.8 inches)
Width:
45 mm
(1.8 inches)
Depth:
105 mm
(4.1 inches)
Agency Approvals
• UL508 listed, c-UL, CE, IP65 (NEMA 4X), File #E102269
• CE:
89/336/EEC (EN 61326)
73/23/EEC (EN61010-1)
1
Electromechanical relays warranted for 100,000 closures only.
Solid-state switching devices recommended for applications
requiring fast cycle times or extended service life.
2
Switching inductive loads (relay coils, etc.) requires using an RC
suppressor.
3
Operating environment is 0 to 60°C for line voltage exceeding 240V.
4
To effect IP65 (NEMA 4X) rating requires a minimum mounting
panel thickness of 1.5 mm (0.06 inch) and surface finish not
rougher than 812
µ
mm (0.32
µ
inch). Use Greenlee punch 60287.
Specifications