beautypg.com

Specifications – Watlow QPAC User Manual

Page 27

background image

QPAC User's Guide

27

Appendix

Specifications

• Input impedance 250Ω (move jumper for 5kΩ voltage input), or manual

control input

• Soft start approximately 6 seconds upon power-up, 1 second upon set

point change

• Current and interstage transformers included.
• Available on Q01 and Q33 models only.
Line Voltage/Power
• 50/60 Hz Å (ac) line frequency, Q32 and Q33 calibration line frequency

dependent

• Voltage: ±10%, 120, 208, 240, 277, 380, 415, 480, 575VÅ (ac)

Line Voltage Compensation
• 10%Δ in line, 2%Δ in load in the 30% to 70% power region (AF, AL and BV)
Power Dissipation (Watts)
• 1.5 watts/amps per controlled leg
Isolation
• Command signal to load 1250VÅ (ac) minimum

Linearity
• 2%, 30% to 70% power region (All units except CA & CD)
Off-State Leakage Current
• 20mA @ 480VÅ (ac)

SCR Protection
• Semiconductor fuses provided
• dv/dt 200V/µsec minimum
• MOV and RC snubber network standard (MOV comes only on Q33

[3-phase, 3-leg])

• (Q32) third leg fuse kit may be used, but not required, with 3-phase, 2-leg

models

Mounting
• Heat sink fins must be mounted in vertical orientation
Operating Environment
• 0 to 50°C (32 to 122°F)
• 0 to 90% RH, non-condensing
Storage Temperature
• -40 to 85°C (-40 to 185°F)
Options
• Manual Control Kit for process input cards (1kΩ potentiometer) #08-5362
• 240VÅ (ac) cooling fans in place of 120VÅ (ac) cooling fans

Weight

Phase

Amps

Q01

3ø,2 leg

Q32

3ø,3 wire

Q33

150

6.8 kg (15 lbs)

16.3 kg (36 lbs)

22.7 kg (50 lbs)

200

6.8 kg (15 lbs)

16.3 kg (36 lbs)

22.7 kg (50 lbs)

300

6.8 kg (15 lbs)

16.3 kg (36 lbs)

22.7 kg (50 lbs)

400 to 600

19.9 kg (44 lbs)

38.5 kg (85 lbs)

45.4 kg (100 lbs)

800 to 1,000

22.2 kg (49 lbs) 54.4 kg (120 lbs) 61.2 kgs (135 lbs)