QPAC User's Guide

17

Chapter 2: Install & Wire

Input Wiring

AL Control Card,Current
Transformer Selection.

Example of Current
Transformer (CT)
Connections One CT, 150
Amps and Above, 1Ø.

CT

AL Card

Bk

Bk

Bk

16-0176

Transformer

Red

Red

Wh

TB-3

TB-2

5A

20mA

5A:20mA

T2

T1

1

5

Load

Soft Start

(Available on the Phase Angle input cards AF and AL only.)

Some heater elements change resistance with temperature. Certain types,
such as tungsten, change resistance very fast (tungsten increases resis-
tance over 16 times from cold to hot). By slowly increasing the voltage to the
heater, the heater element is warmed to full resistance by the time full volt-
age is applied, thus reducing excessive surge currents. Soft start time on the
QPAC is about 6 seconds from power-up. If the QPAC is forced into emer-
gency shut down (ESD) the QPAC will restart soft. Soft start is only available
on phase angle models.

AL Control Card Current Transformer Connections

Phase Angle Current Limit Option

The AL Control Card is wired to a transformer from the load line of the
QPAC. The transformer is wired into pins 1 and 2 of connector TB3 of the AL
card. The following table and figures show the transformer connections for
different load configurations and currents.

Current Transformer

(Part Number)

Description

Interstage

Transformer

Not Used

5A : 20mA Interstage Transformer

16-0176

16-0008

150A : 5A Current Transformer

16-0176

16-0045

200A : 5A Current Transformer

16-0176

16-0073

300A : 5A Current Transformer

16-0176

0004-0286-0400

400A : 5A Current Transformer

16-0176

0004-0286-0500

500A : 5A Current Transformer

16-0176

0004-0286-0600

600A : 6A Current Transformer

16-0176

0004-0287-0800

800A : 5A Current Transformer

16-0176

0004-0288-1000

1,000A : 5A Current Transformer

16-0176