QPAC User's Guide

Chapter 2: Install & Wire

QPAC-01 Output Wiring
for 150 to 1,000A Units.

WARNING: Shock Hazard
Heatsinks are electrically
Live.

ç

CAUTION:
Check terminals for
tightness before ap-
plying power and then
recheck terminals after
one day of operation.
Loose connections can
damage the SCR.

NOTE:
A circuit breaker is re-
quired in addition to the
semiconductor fuses.
All semiconductor fuses
are mounted on board
the QPAC models 400 to
1,000. Where third-leg
fusing is selected, addi-
tional space is required.

NOTE:
QPAC models Q01, Q32
and Q33 up to 300A and
575V

Å

(ac) are agency

listed. QPAC models Q01
and Q32 up to 1,000A
and 480V

Å

(ac) are

agency listed. Q33 400
to 1,000A are not agency
listed.

WARNING:
To avoid damage to
property and equipment,
and/or injury or loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the QPAC.
Failure to do so could
result in damage and/or
injury or death.

Output Wiring

*1 NOTE: On 120V

Å

(ac) or 277V

Å

(ac), L2 is

neutral and cannot be
broken.
*2 NOTE: A contactor is
required if a high limit
control is used.
*3 NOTE: A separate
disconnect is required
for the fan(s) if used.
*4 NOTE: Use 14- to 16-
gauge wire for control
power only.

Circuit

Breakers

or

Disconnects

Contactors
If Required

On-board,

factory

installed

semicon-

ductor

fuses

Heater
Load

L1

L2

Fan 120VÅ (ac)/20W

L2

L1

T1

*1

*2

*3

*4

1A Fuse

L1

L2

G

Circuit

Breakers

or

Disconnects

Contactors
If Required

On-board

factory-

installed

semi-

conductor

fuses

Heater

Load

Fan 120VÅ (ac)/20W

L1
L2

L2

L1

L1

T1

L2

L3

T3

L3

1A
fuse

*2

*3

*4

G

QPAC-32 Output Wiring
for 150 to 1,000A Units.