Setup menu (cont.) – Watlow EZ-ZONE PM Express Limit User Manual

Page 25

background image

EZ-ZONE PM Limit Express

• 25 •

Setup Menu

Setup Menu (cont.)

Display

Parameter Name Description

Range (

Defaults are shown bold)

LoC

[LoC]

Lockout Menu

Set the security clearance level. The user

can access the selected level and all lower

levels.

Appears if: Always

1 to 5
1 Operations Menu (read only)*
2 Operations Menu (Set point R/W)*
3 Operations Menu (Set point R/W, Control Mode R/W)*
4 Operations Menu R/W access)*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level

[Sen]

[ SEn]

Sensor Type

Set the analog sensor type to match the

device wired to this input.

Appears if: Always.

[``tC]

Thermocouple

[`MA]

Milliamps dc

[uolT]

Volts dc

[r0;1H]

RTD 100 Ω

[Lin]

[ Lin]

Linearization

Set the linearization to match the thermo-

couple type wired to this input.

For example, select [```H] for a type K

thermocouple.

Appears if: Sensor Type is set to Thermo-

couple.

[`b]

B

[`J]

J

[`t]

T

[`c]

C

[`H]

K

[`d]

D

[`n]

N

[`e]

E

[`r]

R

[`f]

F

[`S]

S

[``t;C]

[ t.C]

Thermistor Curve

Select a curve to apply to the thermistor

input.

[```A]

Curve A, [```b] Curve B, [```C] Curve C

[CUSt]

Custom

[``r;r]

[ r.r]

Resistance Range

Set the maximum resistance of the thermis-

tor input.

[```5]

5K, [``10] 10K, [``20] 20K, [``40] 40K

[`dEC]

[ dEC]

Decimal

Set the precision of the displayed value.

Appears if: Always.

[```0]

Whole

[``0;0]

Tenths

[`0;00]

Hundredths

[`C_F]

[ C_F]

Display Units

Select which units will be displayed.

Appears if: Always.

[```F]

°F

[```C]

°C

[`r;Lo]

[ r.Lo]

Limit Set Point - Range Low

Sets the low limit of the set point adjustment

using a T/C and RTD; scales for process

inputs.

Appears if: Always.

-1,999.00 to 9,999.000 °F or Units
-1,110.555 to 5,555.000 °C
0.0