Setup Menu

[`loC]

Lockout Menu

[`SEn]

Sensor Type

[`Lin]

Linearization

[``t;C]

Thermistor Curve

[``r;r]

Resistance Range

[`deC]

Decimal

[`C_F]

Display Units

[`r;lo]

Limit Set Point Range Low

[`r;hi]

Limit Set Point Range High

[`fn1]

Function Output One

[`fn2]

Function Output Two

[`l;sd]

Limit Sides

[`l;hy]

Limit Hysteresis

[`A;ty]

Alarm Type

[`A;hy]

Alarm Hysteresis

[`A;lg]

Alarm Logic

[`A;lA]

Alarm Latching

[`A;bl]

Alarm Blocking

[`A;si]

Alarm Silencing

[A;dsp]

Alarm Display

[par1]

Upper or Left Display

[par2]

Lower or Right Display

[`Ad;s]

Zone Address

Setup Menu

To enter the Setup Menu push and hold

the up and down arrow keys for ap-

proximately 3 seconds. Once there, push

the green advance key to scroll through

to the prompt of choice and then use

the up and down arrow keys to change

the range. At any point within the Setup

menu to return to the default display

push the Reset

key.

Setup Menu (cont.)

Display

Parameter Name Description

Range (

Defaults are shown bold)

LoC

[LoC]

Lockout Menu

Set the security clearance level. The user

can access the selected level and all lower

levels.

Appears if: Always

1 to 5
1 Operations Menu (read only)*
2 Operations Menu (Set point R/W)*
3 Operations Menu (Set point R/W, Control Mode R/W)*
4 Operations Menu R/W access)*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level

[Sen]

[ SEn]

Sensor Type

Set the analog sensor type to match the

device wired to this input.

Appears if: Always.

[``tC]

Thermocouple

[`MA]

Milliamps dc

[uolT]

Volts dc

[r0;1H]

RTD 100 Ω

[Lin]

[ Lin]

Linearization

Set the linearization to match the thermo-

couple type wired to this input.

For example, select [```H] for a type K

thermocouple.

Appears if: Sensor Type is set to Thermo-

couple.

[`b]

B

[`J]

J

[`t]

T

[`c]

C

[`H]

K

[`d]

D

[`n]

N

[`e]

E

[`r]

R

[`f]

F

[`S]

S

[``t;C]

[ t.C]

Thermistor Curve

Select a curve to apply to the thermistor

input.

[```A]

Curve A, [```b] Curve B, [```C] Curve C

[CUSt]

Custom

[``r;r]

[ r.r]

Resistance Range

Set the maximum resistance of the thermis-

tor input.

[```5]

5K, [``10] 10K, [``20] 20K, [``40] 40K

[`dEC]

[ dEC]

Decimal

Set the precision of the displayed value.

Appears if: Always.

[```0]

Whole

[``0;0]

Tenths

[`0;00]

Hundredths

[`C_F]

[ C_F]

Display Units

Select which units will be displayed.

Appears if: Always.

[```F]

°F

[```C]

°C

[`r;Lo]

[ r.Lo]

Limit Set Point - Range Low

Sets the low limit of the set point adjustment

using a T/C and RTD; scales for process

inputs.

Appears if: Always.

-1,999.00 to 9,999.000 °F or Units
-1,110.555 to 5,555.000 °C
0.0