Symptom/condition

Probable Cause

Solution

x If using the analog input, is the

current or voltage at [O] or [OI]?

x Check the wiring.
x Check the potentiometer or

signal generating device.

x Is the load too heavy?

x Reduce the load.
x Heavy loads activate the

overload restriction feature
(reduces output as needed).

The motor speed will not

reach the target frequency

(desired speed).

x Is the inverter internally limiting

the output frequency?

x Check max frequency setting

(A004)

x Check frequency upper limit

setting (A061)

The rotation is unstable

x Is the load fluctuation too great?
x Is the supply voltage unstable?
x Is the problem occurring at a

particular frequency?

x Increase the motor capacity

(both inverter and motor).

x Fix power supply problem.
x Change the output frequency

slightly, or use the jump
frequency setting to skip the
problem frequency.

The RPM of the motor does

not match the inverter

output frequency setting.

x Is the maximum frequency setting

A004 correct?

x Does the monitor function D001

display the expected output
frequency?

x Verify the V/f settings match

motor specifications.

x Make sure all scaling (such as

A011 to A014) is properly set.

x Was power turned OFF after a

parameter edit but before pressing
the Store key?

x Edit the data and press the

Store key once.

No download has
occurred

x Edits to data are permanently

stored at power down. Was the time
from power OFF to power ON less
than six seconds?

x Wait six seconds or more

before turning power OFF
after editing data.

Inverter

data us not

correct

The download
to the inverter
was attempted

x Was the power turned OFF within

six seconds after the display
changed from REMT to INV?

x Copy the data to the inverter

again, and keep power ON for
six seconds or more after
copying.

True for
certain
parameters

x Is the inverter in Run Mode? Some

parameters cannot be edited during
Run Mode.

x Put inverter in Stop Mode

(press the Stop/reset key).
Then edit the parameter.

A
parameter
will not
change
after an
edit
(reverts to
old
setting).

True for all
parameters

x If you’re using the [SFT] intelligent

input (software lock function)—is
the [SFT] input ON?

x Change the state of the SFT

input, and check the B031
parameter (SFT mode).