Use one BRD-E3 braking unit for the braking torque listed in the following table.
Note the column meanings in the tables:
x
Column “A” = Average braking torque from 60Hz to 3Hz.
x
Column “B” = Average braking torque from 120Hz to 3Hz.
X200 Inverter 200V Models
Braking Torque with BRD-E3 Braking Unit
External resistor added
Using built-in
resistor only
HRB1
HRB2
HRB3
Model Number
HP
Braking
torque
without
braking unit
A
B
A
B
A
B
A
B
002SFEF/NFU
1/4
50%
150%
120%
004SFEF/NFU
1/2
50%
150%
120%
005SFEF
3/4
50%
150%
120%
007SFEF/NFU
1
50%
100%
80%
150%
120%
011SFEF
1.5
50%
60%
60%
100%
80%
015SFEF/NFU
2
50%
50%
50%
100%
80%
022SFEF/NFU
3
20%
50%
50%
100%
80%
037LFU
5
20%
40%
40%
60%
60%
100%
100%
150%
120%
055LFU
7.5
20%
30%
30%
50%
50%
70%
70%
100%
80%
075LFU
10
20%
20%
20%
40%
40%
50%
50%
80%
80%
Connect a second braking unit in parallel for additional braking torque listed in the
following table.
X200 Inverter 200V Models
Braking Torque with BRD-E3 Braking Unit
External resistor added
Using built-in
resistor only
HRB1
HRB2
HRB3
Model Number
HP
Braking
torque
without
braking unit
A
B
A
B
A
B
A
B
002SFEF/NFU
1/4
50%
150%
120%
004SFEF/NFU
1/2
50%
150%
120%
005SFEF
3/4
50%
150%
120%
007SFEF/NFU
1
50%
150%
120%
011SFEF
1.5
50%
100%
80%
015SFEF/NFU
2
50%
100%
80%
022SFEF/NFU
3
20~40%
70%
70%
150%
120%
037LFU
5
20~40%
50%
50%
110%
90%
055LFU
7.5
20%
30%
30%
80%
80%
100%
100%
150%
150%
075LFU
10
20%
30%
30%
60%
60%
80%
80%
100%
100%
5
6
5
−6