Selection of automatic restart
mode
B001
IPS POWR
ALM
Select inverter restart method,
Four option codes:
00
}Alarm output after trip, no
automatic restart
01
}Restart at 0Hz
02
}Resume operation after
frequency pull-in
03
}Resume previous freq. after
freq. pull-in, then decelerate
to stop and display trip info
U
00
00
Allowable under-voltage
power failure time
B002
IPS Time
0001.0s
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to 25
sec. If under-voltage exists longer
than this time, the inverter trips,
even if the restart mode is
selected.
U
1.0
1.0
sec.
Retry wait time before motor
restart
B003
IPS Wait
0001.0s
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
U
1.0
1.0
sec.
Instantaneous power failure /
under-voltage trip alarm
enable
B004
IPS TRIP
OFF
Two option codes:
00
}Disable
01
}Enable
U
00
00
Number of restarts on power
failure / under-voltage trip
events
B005
IPS RETRY
16
Two option codes:
00
}Restart 16 times
01
}Always restart
U
00
00
Frequency Pull-in Restart
“B” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Start freq to be used in case
of frequency pull-in restart
B011
FSch Md
CUTOFF
Three option codes:
00
}freq at previous shutoff
01
}start from max. Hz
02
}start from set frequency
U
00
00
Deceleration rate of
frequency pull-in restart
setting
B029
FSch CNS
0000.5s
Sets the deceleration rate when
frequency pull-in restart, range is
0.1 to 3000.0, resolution 0.1
U
0.5
0.5
sec.
Current level of frequency
pull-in restart setting
B030
FSch LVL
002.60A
Sets the current level of
frequency pull-in restart, range is
0.2*inverter rated current to
2.0*inverter rated current,
resolution 0.1
U
Rated
current