“C” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Overload level setting
C041
OV LVL
001.60A
Sets the overload signal level
between 0% and 200% (from 0 to
two time the rated current of the
inverter)
U
Rated current
for each
inverter model
A
Overload level setting,
2nd motor
C241
2OV LVL
001.60A
Sets the overload signal level
between 0% and 200% (from 0 to
two time the rated current of the
inverter)
U
Rated current
for each
inverter model
A
Frequency arrival setting
for acceleration
C042
ARV ACC
0000.0Hz
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
U
0.0
0.0
Hz
Frequency arrival setting
for deceleration
C043
ARV DEC
0000.0Hz
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
U
0.0
0.0
Hz
PID deviation level setting
C044
ARV PID
003.0%
Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%
U
3.0
3.0
%
PID FBV function high
limit
C052
PID LtU
0100.0%
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0 to
100%
U
100.0 100.0
%
PID FBV function variable
low limit
C053
PID LtL
0000.0%
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
U
0.0
0.0
%