Input Function Summary Table

Option

Code

Terminal

Symbol

Function Name

Description

ON

Adds the A145 (add frequency) value to the output
frequency

50

ADD

ADD frequency
enable

OFF

Does not add the A145 value to the output frequency

ON

Force inverter to use input terminals for output
frequency and Run command sources

51

F-TM

Force Terminal
Mode

OFF

Source of output frequency set by A001 and source of
Run command set by A002 is used

ON

To charge up the internal boot-strap capacitor so to
start motor immediately after the RUN command is
given.

52

RDY *

Inverter Ready

OFF

Inverter operates normal.

ON

The inverter uses 2nd motor parameters for generating
frequency output to motor. The selection of 1st or 2nd
motor is available during Stop Mode or Run Mode.

53

SP-SET

Special set

OFF

The inverter uses 1st (main) motor parameters for
generating frequency output to motor.

ON

Inverter recognizes that the emergency signal is given,
and shuts off the output.

Refer to “Safe Stop” on page 4-32.

64

EMR *

Emergency

Stop

OFF

Inverter operates normal

ON

(input ignored)

255

-

(No function)

OFF

(input ignored)

NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F001 or change the value of F001 while the inverter is in Run Mode (motor
running). If it is necessary to check the value of F001 during Run Mode, lease monitor
D001 instead of F001.

HIGH VOLTAGE: When set RDY function ON, there will be a voltage appears at motor
output terminals U, V and W even if the motor is in stop mode. So never touch the
inverter power terminals even the motor is not running.

NOTE: The EMR is not programmable, but will be assigned automatically when the
hardware switch S8 is made ON. When the EMR is assigned, function assignments of
terminal 3, 4 and 5 are automatically changed as follows. Please also refer to
Emergency Stop paragraph.

Emergency Stop switch condition

Terminal

Number

Default setting

Emergency Stop switch

S8 = OFF

Emergency Stop switch

S8 = ON

Emergency Stop switch

S8 = ON

Æ OFF

1

FW

FW

FW

2

RV

RV

RV

3

CF1

EMR

[HW based for 1b input]

- (No func.)

4

CF2 [US ver. :USP]

RS

[HW based for 1a input]

RS

[Normal 1a]

5

RS

(PTC assignable)

- (No func.)

- (No func.)

3

53

Config

uri

ng Driv

e

Parameters

3

−53

&RQ¿JXULQJ'ULYH

Parameters