Output Logic and Timing

Logic Output Function – The inverter has a built-in logic output feature. You can select
any two of the other nine intelligent output options for internal inputs. Then, configure
the logic function to apply the logical AND, OR, or XOR (exclusive OR) operates as
desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021,
or C026 to route the logical result to terminal [11] or the relay terminals.

The following table shows all four possible input combinations with each of the three
available logic operations.

Input Status

[LOG] Output State

A

B

AND

OR

XOR

0

0

0

0

0

0

1

0

1

1

1

0

0

1

1

1

1

1

1

0

“C” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Input A select for logic
output

C141

LogicOut1

RUN

U

00

00

Input B select for logic
output

C142

LogicOut2

FA1

11 programmable functions
available for logic (discrete)
outputs
00

}RUN

01

}FA1

02

}FA2

03

}OL

04

}OD

05

}AL

06

}Dc

07

}FBV

08

}NDc

09

}LOG

10

}ODc

43

}LOC

U

01

01

Logic function select

C143

LogicOPE

AND

Applies a logic function to calculate
[LOG] output state,
Three options:
00

}[LOG] = A AND B

01

}[LOG] = A OR B

02

}[LOG] = A XOR B

U

00

00

Intelligent outputs
used as internal
inputs:

RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC

Input A

C141

RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC

Input B

C142

Logic function

AND, OR, XOR

C021

11

AL1

AL0

AL2

C026

3

63

Config

uri

ng Driv

e

Parameters

3

−63

&RQ¿JXULQJ'ULYH

Parameters