Output logic and timing – XLT Hitachi X200 User Manual
Page 146
Output Logic and Timing
Logic Output Function – The inverter has a built-in logic output feature. You can select
any two of the other nine intelligent output options for internal inputs. Then, configure
the logic function to apply the logical AND, OR, or XOR (exclusive OR) operates as
desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021,
or C026 to route the logical result to terminal [11] or the relay terminals.
The following table shows all four possible input combinations with each of the three
available logic operations.
Input Status
[LOG] Output State
A
B
AND
OR
XOR
0
0
0
0
0
0
1
0
1
1
1
0
0
1
1
1
1
1
1
0
“C” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Input A select for logic
output
C141
LogicOut1
RUN
U
00
00
Input B select for logic
output
C142
LogicOut2
FA1
11 programmable functions
available for logic (discrete)
outputs
00
}RUN
01
}FA1
02
}FA2
03
}OL
04
}OD
05
}AL
06
}Dc
07
}FBV
08
}NDc
09
}LOG
10
}ODc
43
}LOC
U
01
01
Logic function select
C143
LogicOPE
AND
Applies a logic function to calculate
[LOG] output state,
Three options:
00
}[LOG] = A AND B
01
}[LOG] = A OR B
02
}[LOG] = A XOR B
U
00
00
Intelligent outputs
used as internal
inputs:
RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC
Input A
C141
RUN, FA1, FA2,
OL, OD, AL, Dc,
FBV, NDc, ODc,
LOC
Input B
C142
Logic function
AND, OR, XOR
C021
11
AL1
AL0
AL2
C026
3
63
Config
uri
ng Driv
e
Parameters
3
−63
&RQ¿JXULQJ'ULYH
Parameters