Troubleshooting Tips

The table below lists typical symptoms and the corresponding solution(s).

Symptom/condition

Probable Cause

Solution

x Is the frequency command source

A001 parameter setting correct?

x Is the Run command source A002

parameter setting correct?

x Make sure the parameter

setting A001 is correct

x Make sure the parameter

setting A002 is correct

x Is power being supplied to terminals

[L1], [L2], and [L3/N]? If so, the
POWER lamp should be ON.

x Check terminals [L1], [L2],

and [L3/N], then [U/T1],
[V/T2], and [W/T3].

x Turn ON the power supply or

check fuses.

x Is there an error code

E X X

displayed?

x Press the Func. key and

determine the error type.
Eliminate the error cause,
then clear the error (Reset).

x Are the signals to the intelligent

input terminals correct?

x Is the Run Command active?
x Is the [FW] terminal (or [RV])

connected to [PCS] (via switch, etc.)

x Verify the terminal functions

for C001–C005 are correct.

x Turn ON Run Command

enable.

x Supply 24V to [FW] or [RV]

terminal, if configured.

x Has the frequency setting for F001

been set greater than zero?

x Are the control circuit terminals

[H], [O], and [L] connected to the
potentiometer?

x Set the parameter for F001 to

a safe, non-zero value.

x If the potentiometer is the

frequency setting source,
verify voltage at [O] > 0V.

The inverter
outputs [U], [V],
[W] are not
supplying
voltage

x Is the RS (reset) function or FRS

(free-run stop) function ON?

x Turn OFF the command(s)

Inverter
outputs [U],
[V], [W] are
supplying
voltage.

x Is the motor load too heavy?

x Reduce the load, and test the

motor independently.

The motor

will not run

The optional
remote
operator is
used (SRW).

x Are the operational settings

between the remote operator and
the inverter unit correct?

x Check the operator type

setting.

x Are the connections of output

terminals [U/T1], [V/T2], and [W/T3]
correct?

x Is the phase sequence of the motor

forward or reverse with respect to
[U/T1], [V/T2], and [W/T3]?

x Make connections according to

the phase sequence of the
motor. In general:
FWD = U-V-W, and REV=U-
W-V.

The direction of the motor is

reversed

x Are the control terminals [FW] and

[RV] wired correctly?

x Is parameter F004 properly set?

x Use terminal [FW] for

forward, and [RV] for reverse.

x Set motor direction in F004.