System Sensor FAAST Networking User Manual
Page 32
![background image](/manuals/352663/32/background.png)
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Networking
32
Server Requirements
The mail server will accept messages from the FAAST detector and attempt to relay them to the specified recipients. This server must
meet the following requirements:
• Accept and deliver messages from the e-mail address specified in the Sender Account field.
• Accept and relay SMTP messages from port 25 without requiring authentication.
• Have connectivity and DNS service to networks (such as the Internet) where recipient mail servers reside.
E-mail Client Requirements
Once connectivity to the mail server is established, the integrated SMTP client will communicate with the server to deliver alarm and
fault e-mail notifications. For the client to work properly, the following are required:
• The Sender Account field is used to populate the SMTP “From” field and specifies where an e-mail message originates. This
field should be populated with an e-mail address specifically reserved for the detector. An e-mail account may need to be cre-
ated and added to the mail server by the server administrator.
• Up to 6 recipient e-mail addresses and desired notifications must be configured.
E-mail Client Configuration
The integral SMTP client is configured using the PipeIQ software. Before attempting to configure the e-mail client, the IP configuration
of the detector should be completed and network connectivity verified. For instructions, see the TCP/IP Connectivity section earlier
in this guide.
1. Start the PipeIQ software application.
2. Open the project for it using File -> Open.
3. Double-click the desired device to open the Configuration window.