User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

Action

1.

Turn the input switch (Q001) to position “1”.
If dual utility is present, turn the bypass
input switch (Q010) to position “1”.

2.

Wait 10 sec. Open the UPS front door and
press the green “ON“ key

3.

Press

on the keyboard

4.

Press

or

on the keyboard until

5.

Press

on the keyboard

6.

Press

on the keyboard

7.

Check lamp indication on the service bypass

The green lamp (H002)

panel

above the output switch
handle (Q002) lights

8.

Turn the output switch (Q002) to position “1“

Now the green lamp (H003)
above the bypass switch
handle (Q003) lights too

9.

Turn the bypass switch (Q003) to position “0“

Only the green lamp (H003)
above the bypass switch
handle (Q003) lights

10. Press

on the keyboard

11. Press

or

on the keyboard until

12. Press

on the keyboard

13. Press

on the keyboard

14. Press

on the keyboard

15. Press

on the keyboard

Single Utility

Dual Utility

2.6.2

Switching the system from external bypass into normal
UPS operation

Lamp indication
on bypass panel

Display shows

No lamps on the bypass
panel light any longer

Display shows

Stop, Start & Operating the External Service Bypass Panel

NOTE:
If battery has been discon-
nected please refer to
“Starting Up” in Chapter 2.5.1 to
connect battery(-ies) again.

**System OFF**

Normal operation

load power 0%

Bypass operation

: NO

Bypass operation

: YES

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power xx%