System specifications, 0 system specifications – APC Silcon DP300E Series User Manual
Page 37
37
User Guide Silcon DP300E Series 480V 400-500kVA
7OA0004 US rev. 02
10.0 System Specifications
10.1 Technical data
Input
Voltage
3 x 480V
Voltage tolerance
Normal operation
±
15%
Bypass operation
±
10% (standard)
±
4, 6, 8% (programmable)
Frequency
60Hz
±
6% standard
±
0,5-8% (programmable)
Input PF
Load 25% min. 0,97
Load 100% min. 0,99
Current distortion
Max. 5%
Output
Voltage
3 x 480V
Voltage tolerance
±
1% static, sym. load
±
3% static, asym. load
±
5% 0-100% load step
Voltage distortion
Max. 3%, linear load
Max. 5%, non-linear load
(Silcon DP3400E-DP3500E)
Load power factor
0,9 lead to 0,8 lag
Frequency
60Hz (utility synchronized)
±
0,1% free running
Overload capacity
Normal operation
200% - 60 secs.
Normal operation
125% - 10 min.
Battery operation
150% - 30 secs.
Bypass operation
125% - cont.
General
Ambient temperature
0-40
°
C/32-104
°
F
(Above 25
°
C/77
°
F the battery life
time is reduced)
Humidity
Max. 95%, non condensing
Protection class
NEMA 1
Safety
EN50091-1
UL 1778
Emission and Immunity
EN50091-2
Static bypass switch
Built-in
Auto restart
Programmable
Economy mode
Programmable
System Specifications