User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

Programming Parameters

4.3.2 Programming example – change charge voltage to 446V*

Action

Display shows

1.

Press

and

simultaneously to open

for password input

2.

Enter password xx xx xx by pressing

3.

Press

or

until

4.

Press

5.

Press

to store

6.

Wait about 1 second

7.

Press

to exit

4.3.3 Programming example - change to output isolation transformer

present**

Action

Display shows

1.

Press

and

simultaneously to open

for password input

2.

Enter password xx xx xx by pressing

3.

Press

or

until

4.

Press

for change

5.

Press

to store

6.

Wait about 1 second

7.

Press

to exit

Last selected

parameter

Boost charge voltage

: 438

Boost charge voltage

: 446

Data stored

Boost charge voltage

: 446

Normal operation

load power XX%

Key in password

:

Key in password

:

Last selected

parameter

Normal operation

load power XX%

Isolation trafo output

: YES

Data stored

Isolation trafo output

: NO

Isolation trafo output

: YES

** The other parameters are
selected by pressing the

key

as step 4 in example 4.3.3. -
one or more times.

NOTE:
Only for APC personnel and
certified local APC personnel.

* For charge voltages, battery
warnings and shut down
voltages, and high battery
temperature, the parameter is
changed by entering the actual
value like example 4.3.2.