User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

WARNING!
If the UPS is out of service for
more than 48 hours the
connected batteries might be
damaged. Refer to total
“Switching off“ as described in
chapter 2.4.1.

2.7.1

Bypassing the parallel UPS system

Action

Point 1-4 can be carried out with any of the parallel systems, however this will switch
all systems into bypass operation.

1.

Press

on the keyboard

2.

Press

or

on the keyboard until

3.

Press

on the keyboard

4.

Press

on the keyboard

All systems will transfer to bypass operation

Do not switch off any of the UPS systems until
point 5-8 has been carried out

5.

Check lamp indication on the bypass panel

The green lamp (H003)
above the bypass switch
handle (Q003) lights

6.

Turn the external bypass switch (Q003)

The green lamp (H004)

to position “1“

above the output switch
(Q004) and the green lamps
(H002) above the output
switch handles (Q002) light

7.

Turn the output switch (Q004) to position “0”

H003 turn off
H002 & H004 still lights

8.

Turn all output switches (Q002) to position “0“

H002 & H004 still lights

9.

Open the front door and press the red “OFF”
push-button in any of the systems.
The acoustic alarm sounds for 30 secs.*

Repeat for (all) other system(s)

2.7

Operating the external service bypass switch, parallel
systems

DP300E

DP300E

Q010a

Q001a

Q002a

Q004

Q010b

Q001b

Q002b

Utility 1

Q003

Service bypass switch

H003

Load

Utility 2

H004

H002b

H002a

H010a

H010b

Single Utility

Dual Utility

Display shows

Display shows

Lamp indication
on bypass panel

Stop, Start & Operating the External Service Bypass Panel

Bypass operation

: NO

Bypass operation

: YES

Bypass operation

**System OFF**

DP300E

DP300E

Q003

Service

bypass

switch

H003

Q001a

Q001b

Q002b

Q004

Q002a

Load

Utility

H004

H002a

H002b