beautypg.com

Measurements, 0 reading out measurements – APC Silcon DP300E Series User Manual

Page 24

background image

24

User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

Measurements

98.01.16
10.22,13

Mains 1 voltage

480 480 480 V

ac

Battery current

+ 20 A

dc

Mains 1 Current

100 100 100 A

ac

Battery voltage

438 437 V

dc

Output voltage

480 480 480 V

ac

Output current

180 180 180 A

ac

Output frequency

60Hz

Battery temp.

25ºC

Output peak current

255 255 255 A

Mains 2 voltage

480 480 480 V

ac

Mains 2 Current

100 100 100 A

ac

5.0

Reading Out Measurements

Press as indicated below one key or two keys simultaneously (values used are only
random for illustration):

Action

Display shows

Description

Year, month, day
Hour, minute, second

Utility 1 voltage
is 3 x 480 V

ac

Utility 1 current
is 3 x 100 A

ac

Utility 2 voltage
is 3 x 480 V

ac

Utility 2 current
is 3 x 100 A

ac

Battery voltage is 438 V

dc

on batt.1.

437 V

dc

on batt.2.

Charging current is (+) 20 A

dc

(Discharging current (

÷

))

Output voltage
is 3 x 480 V

ac

Output current
is 3 x 180 A

ac

Output frequency
is 60 Hz

Battery temperature
is 25

°

C (77

°

F)

Output peak current
is 3 x 255 A

Returns to normal status indication.
If not pressed, automatic switch back
will be performed after 20 seconds.

Battery load in procent.
Left battery capacity in procent.

NOTE:
Utility = Mains

Normal operation

load power xx%

Batt. load : 0

Batt. tank : 100