Programming parameters – APC Silcon DP300E Series User Manual

Page 20

background image

20

User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

4.4

Programming of battery monitor

Action

Display shows

1.

Press

and

simultaneously to open

for password input

2.

Enter password xx xx xx by pressing

3.

Press

or

until

4.

Enter the expected back-up time in min. at
100% ohmic (pf = 1) load, when the inverter
has a mean efficiency of approx. 96%

Press

I.e. 14.0 min.

5.

Press

to store data

6.

Press

or

until

7

Press

to set Ah for battery

8.

Press

to store data

9.

Press

to exit

Installation of new batteries:
When installing new batteries the procedure in section 4.4 MUST be carried out,
otherwise the monitor may give false alarms.

Programming Parameters

Key in password

:

Last selected

parameter

Expected back-up

time [min.]: XXX.X

Expected back-up

time [min.]: 14.0

Data stored

Battery capacity

in [Ah]: XX.X

Battery capacity

in [Ah]: 7.0

Data stored

Normal operation

load power XX%

NOTE:
Only for APC personnel and
certified local APC personnel.