Programming parameters, 0 programming parameters – APC Silcon DP300E Series User Manual

Page 16

background image

16

User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

4.0

Programming Parameters

4.1

General

Some operating parameters can be programmed directly from the keyboard. Unless
you are quite sure of the consequence of changing the following parameters, please
contact your local APC dealer for assistance.
Parameters are programmed as shown in the example 4.2.3.

4.2

Parameters

4.2.1

Parameter

Setting*

Comments

Bypass

YES, NO

“YES” will switch the system into
bypass mode

Language

GB, D, F, I,

Language of text in display

DK, S, SF,
NL, PL, CZ,
E, P, SK, H

Autostart

YES, NO

Automatic restart of UPS upon utility return.
Ensures quick battery recharge.

Remote shutdown

YES, NO

Shutdown of UPS by remote signal

active

Remote shutdown

HIGH, LOW Nature of remote shutdown signal polarity

polarity

Remote shutdown time

0, 1, 2, 3, 4

Time delay on remote shutdown of UPS

5, 6, 7, 8, 9
10 min.

Battery capacity test

-

Initiates check of back-up time. The
measured time is from start until it reaches
low DC warning level (See section 8.4)

Battery monitor test**

-

Initiates check of battery condition by
25% discharging.

Automatic battery test**

NO, 3, 6

Activates the battery monitor test in cyclic
intervals (Unit - months)

Battery monitor reset**

-

Pressing the

and

key after

selecting this parameter resets any battery
alarms.

Boost charge

YES, NO

“YES” results in boost charge (10 hours)

Autoboost charge

YES, NO

“YES” results in boost charge after every
battery operation (10 hours)

Enter new date

YYMMDD

Local date can be entered

Enter new time

HHMMSS

Local time can be entered (24 hour clock)

*

Text in bold letters are the standard setting

** Only for systems with battery monitor active

Programming Parameters

NOTE:
The system must not run in
bypass mode for extended
periods of time as the batteries
will not be charged.