Programming parameters – APC Silcon DP300E Series User Manual

Page 18

background image

18

User Guide Silcon DP300E Series 480V 400-500kVA

7OA0004 US rev. 02

4.3

Programming of system configuration parameters

The system configuration parameters are protected by a password because most of
them are critical for correct operation of the system.
Wrong programming can for example destroy the battery or cause loss of
output voltage during operation!!

4.3.1 System configuration parameters

Parameter

Setting*

Comments

Isolation trafo utility

YES, NO

YES if optional input isolation transformer is
present

Isolation trafo output

YES, NO

YES if optional output isolation transformer is
present

Delta soft start time

1, 10, 20,

Input current switching in ramp function.

40 secs.

Higher values used together with smaller/
unstable diesel generators

External SSW present

YES, NO

YES for systems with external static bypass
switch

Normal charge voltage

438

Setting of float charge voltage at 20

°

C /68

°

F

(Aut. compensation for deviations)

Boost charge voltage

438

Setting of boost charge voltage at 20

°

C /68

°

F

(Aut. compensation for deviations)

Low battery warning

346

Warning for discharged battery

Low battery shut down

326

Switches off the system at min. permissible
battery voltage

Synchronization

0.25, 0.5, 1 Synchronisation speed. Higher values used
2, 4 Hz/sec with very unstable utility frequencies

High battery temperature 15-40

°

C

Alarm for too high battery ambient

/59-104

°

F

temperature

35

°

C/95

°

F

Common fault delay

0, 10, 20

Delay before the common fault alarm relay is

30 secs.

activated

Reset operation mode

YES, NO

YES resets system locked in bypass or battery

lock

operation mode caused by system failures
(Only for service personnel)

Highest station address

2-9***

Highest station address in parallel system

Station address

1-9***

Station address in parallel system

Advanced power

None***

Only used in parallel system.

management (APM)

Off: Advanced power management disabled.
Parallel +1: Redundant operation with all units
in operation.
Redundant +1: Redundant operation with
one unit being inactive in parallel system

APM test mode active

YES, NO*** YES, if APM test mode is active (service

personnel only)

Battery connection

Common,

Common if common battery is used in parallel

Separate

system. Separate if separate battery is used

Expected back-up

0,1-999,9

Expected back-up time for UPS in minutes,

time [min.]

5,0

when running at 100% ohmic load.
Time used by the ABM**

Battery capacity

0,1-999,9

Total battery capacity in Ah.

in [Ah]

7,0

Setting used by the ABM**

Programming parameters

** Advanced Battery Monitor

*** Viewable only in a parallel
configuration.

* Text in bold letters are the
factory standard setting

NOTE:
Common battery pack is a
technical possibility.
However, APC recommend
separate battery pack due to a
higher safety degree in con-
nection with redundant/parallel
operation.
The UPS system is prepared
for both solutions.