SIGNAL FOLLOWING CONNECTIONS – The

drive output will linearly follow the analog signal

input.

Models KBVF-27, 29

Wire the isolated* 0 – 5 Volt DC signal input pos-

itive lead (+) to Terminal “P2” and the negative

lead (–) to Terminal “P1”. The terminals are locat-

ed on the lower PC board. With external circuitry,

a 0 – 10 Volt DC analog signal can also be used.

See Figure 18.

*If a non-isolated signal is used, install the

SIVFR Signal Isolator (Part No. 9597). The

SIVFR accepts voltage (0 to ±2.5 thru 0 to

±25 Volts DC) or current (4 – 20 mA DC)

signal inputs. See Section 3.5, on page 10.

Note: For signal following operation, the

Minimum Speed Trimpot (MIN) must be set

fully counterclockwise.

WARNING! The signal input must

be isolated from the AC line. Earth

grounding signal wiring will damage the

drive and void the warranty. It is recom-

mended that the SIVFR – Signal Isolator

and Run/Fault Relay (Part No. 9597) be

installed when using signal following.

Models KBVF-45, 48

The SIVFR is factory calibrated for 0 to ±5

Volt DC signal input. Wire the voltage (0 to

±2.5 thru 0 to ±25 Volt DC) or current (4 –

20 mA DC) signal input to Terminals “SIG1”

(+) and “COM1” (–) of Terminal Block TB1

on the SIVFR. For voltage following, be

sure Jumper J1 (on the SIVFR) is set to the

“VOLT” position (factory setting). For cur-

rent following, set Jumper J1 (on the

SIVFR) to the “CUR” position. See Figures

19 and 20. A jumper must be

installed between Terminals “0V”

and “FWD”, of Terminal Block

TB1, in order for the drive to

operate.

Application Note – In the Voltage

Following Mode, the input will

accept a “+” and “–“ input volt-

age, which will run the motor in

the forward and reverse direction.

Notes: 1. The MIN Trimpot on Models KBVF-45, 48 is not functional. Use the OFFSET Trimpot on

the SIVFR to offset the signal input, as described in Section 13.2.1, on page 23. 2. Do not use the

MAX Trimpot on Models KBVF-45, 48. Use the MAX Trimpot on the SIVFR to scale the signal input,

as described in Section 13.2.2.

19

REV

-5V

TB

1

+5V

0V

FWD

SIG1 COM1

Jumper

0 to ±25

Volts DC

+ V -

CU

R

VO

LT

J1

SIVF

TERMINAL

BLOCK

FIGURE 19 – MODELS KBVF-45, 48

VOLTAGE FOLLOWING SIGNAL INPUT CONNECTION

(0 to ± 2.5 THRU 0 to ± 25 VOLTS DC)

(JUMPER J1 INSTALLED IN “VOLT” POSITION)

REV

-5V

TB

1

+5V

0V

FWD

SIG1

COM1

Jumper

+

-

4 - 20 mA DC

CU

R

VO

LT

J1

SIVF

TERMINAL

BLOCK

FIGURE 20 – MODELS KBVF-45, 48

CURRENT FOLLOWING SIGNAL INPUT CONNECTION

(JUMPER J1 INSTALLED IN “CUR” POSITION)

FIGURE 18 – MODELS KBVF-27, 29

VOLTAGE FOLLOWING SIGNAL INPUT CONNECTION

0 – 5 Volts DC (Isolated)

0 – 10 Volts DC (Isolated)

P1

P2

P3

0 - 5

Volts DC

+

-

V

P1

P2

P3

0 - 10

Volts DC

V

+

-

10k

10k

FIGURE 21 – MANUAL START SWITCH CONNECTION

Jumper Removed

Connector Installed for

Manual Start Switch

CON1

A/M

Manual Start Switch

(Momentary Contacts)

(Push to Run)

White

Black

CON1

This manual is related to the following products: