9

WIRING INSTRUCTIONS

WARNING! Read Safety Warning, on pages 8 and 9, before using the drive. Disconnect

main power when making connections to the drive. To avoid electric shock, be sure to

properly ground the drive.

Application Note – To avoid erratic operation, do not bundle the AC line and motor wires with each other

or with wires from signal following, start/stop contacts, or any other signal wires. Also, do not bundle motor

wires from multiple drives in the same conduit. Use shielded cables on all signal wiring over 12” (30 cm).

The shield should be earth grounded on the drive side only. Wire the drive in accordance with the National

Electrical Code requirements and other local codes that may apply.

Be sure to properly fuse each AC line conductor that is not at ground potential. Do not fuse neutral or

grounded conductors. A separate AC line switch or contactor must be wired as a disconnect so that each

ungrounded conductor is opened. For fuse or circuit breaker selection, see Section 10, on page 22.

17

TABLE 3 – TERMINAL BLOCK WIRING INFORMATION*

9.1

AC LINE CONNECTION – Wire the

AC line input to Terminal Block TB1.

Model KBVF-27 is designed for

single-phase (Terminals “L1”, “L2”) or

3-phase (Terminals “L1”, “L2”, “L3”)

AC line input. Models KBVF-29, 45,

48 are designed for 3-phase

(Terminals “L1”, “L2”, “L3”) AC line

input only. See Figures 1 and 2, on

pages 4 and 5.

Application Note: GFCI Operation –

Do not connect this drive to an AC

power source controlled by a

Ground Fault Circuit Interrupter.

Special software is required for

GFCI operation – contact our Sales

Department.

Model KBVF-27 – Rated for 208/230

Volt single-phase or 3-phase AC line

Input.

Model KBVF-29 – Rated for 208/230

Volt 3-phase AC line input.

Models KBVF-45, 48 – Rated for

400/460 Volt 3-phase AC line input.

9.2

GROUND CONNECTION – Connect the ground wire (earth) to the green ground screw. The ground

screw is located on the heat sink. See Figure 14.

Terminal Block

Maximum Wire Size (Cu)

Recommended Tightening Torque

Designation

Description

Location

AWG

mm

2

in-lbs

kg-cm

TB1

AC Line Input and Motor Wiring

Upper PC Board

12

3.3

12

14

TB1**

Signal Input, Direction Switch,
and Main Speed Potentiometer

SIVFR***

16

1.3

3.5

4

TB2**

Run/Fault Relay Output Contacts

SIVFR***

16

1.3

3.5

4

* Models KBVF-27, 29 contain quick-connect terminals for signal input. Connectors are provided for wiring of Direction Switch and Manual Start Switch.
** Models KBVF-45, 48 only. *** SIVFR – Signal Isolator and Run/Fault Relay is standard on Models KBVF-45, 48 and optional on Models KBVF-27, 29.

Ground (Earth):

see Section 9.2.

(Model KBVF-27 Only):

Single-Phase Connection

(Use L1, L2)

see Section 9.1.

see Section 9.3, on Page 18.

Motor Connection:

(Use L1, L2, L3)

see Section 9.1.

(Models KBVF-27, 29, 45, 48):

3-Phase Connection

L3

Motor

M

OT

OR

AC

LIN

E

L2

L1

W

TB

1

V

U

FIGURE 14 – AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS