1.1.1 Pager (Numeric - CM only)

Setup Menu > Pager

This is the number of the actual pager.

1.1.1 Page on Fault (Yes/No - CM only)

Setup Menu > Pager

Where a pager has been allocated as above, this function determines whether the pager holder is to be
paged when a fault condition is generated by the Command Module.

1.1.1 Page on Alarm (Yes/No - CM only)

Setup Menu > Pager

Where a pager has been allocated as above, this function determines whether the pager holder is to be
paged when a fire alarm condition is generated by the Command Module.

1.1.1 View Event Log (Display - Address 000-127)

Log Menu

This function shows the start and stop time and date of events such as FastLearn, alarm condition and
error messages. The event log can also be downloaded to a PC via the RS232 serial port. See section 8
“Event Log” on page 44 and section 9.5 “Connecting to a PC” on page 49 for further details.

1.1.1 Diagnostics (Test - Address 001-127)

Diagnostic Menu

This function puts the detector into self-test mode. On a Command Module, it tests all detectors on the
loop.

1.1.1 Detector Read (Display - Address 001-127)

Diagnostic Menu

This function displays five values as shown:

009.47%

086 091 087 091

The top value is the detector’s current smoke level reading as a percentage of the full-scale value, and
the bottom four readings are the current flow rates on each pipe as a percentage of the maximum
possible flow rate.

1.1.1 Loop Errors (Display)

Diagnostic Menu

This displays the percentage of loop errors in messages addressed to the detector or Command Module
from the detector loop, along with a count of the number of received messages since the last message
was received on port 1 and port 2 of the RS485 bus.