3 navigating through the menus, Setup menu, Log menu – Hochiki FIRElink-400CM User Manual
Page 15: Diagnostic menu, Reset, Isolate, Exit, Setup menu log menu log menu

FIRElink-400 Air Sampling System – Installation Manual
Page 15 of 58
© 2010 Hochiki Europe (UK) Ltd
9-5-0-346/ISS4/OCT10
The choices available in the main menu are, in order:
Setup menu
contains all the user-programmable functions
Log menu
Allows the user to view historical information such as the event
log (time and date of various events such as alarm or fault
conditions)
Diagnostic menu
Contains a number of detector self-tests
Reset
Clears any latched fault readings or exits from a menu item to its
parent menu. This has the same effect as pressing the
button.
Isolate
Isolates the detector. This has the same effect as isolating with
the
button,
Exit
Exits programming mode
NOTE: The main menu ‘wraps around‘ so that pressing when in Setup menu brings up Exit etc.
4.3 Navigating
Through
the
Menus
To navigate through the main menu options, press
to navigate through the available choices. The
display shows two adjacent items, for example:
Setup menu
Log menu
Log menu
Pressing
would then show
Diagnostic menu
In other words,
selects items lower in the list by effectively scrolling the screen UP, and vice versa for
.
The currently selected item is the upper item of the two and is identified by a trailing arrow as shown (for
a menu) or a trailing dot (for a menu item or single choice such as
Exit
). When you have the menu you
require, press
. This then gives you a choice of the items within the selected menu. For example, to
set the main fire alarm level:
Having entered the
Fire 1 level
, the selected item indicator steps along to the item below it in the
Alarm levels
submenu. Either this can be edited as above, or
can be used to move to the
next choice. Once the last entry in the sub-menu is reached pressing will move you back up to the