beautypg.com

Led status indication, Operation check list – Robertshaw SlimZone CLASSIC ZONE CONTROL SYSTEM User Manual

Page 13

background image

7.

LED STATUS INDICATION

All relay outputs and system status can be verified at the control panel and are indicated
by LEDs (light emitting diodes). Refer to Figure 4.2 for location of the LEDs.

REFERENCE

COLOR

LOCATION

FUNCTION

POWER ON

Green

24VAC terminal

Panel is powered

FAULT

Red

24VAC terminal

Short in system

ZONE 1

Green

Zone 1 terminal

Damper open

ZONE 2

Green

Zone 2 terminal

Damper open

ZONE 3

Green

Zone 3 terminal

Damper open

G

Green

Equipment terminal

Fan relay energized

Y1

Yellow

Equipment terminal

Cooling/compressor relay energized

W1

Orange

Equipment terminal

Heating relay energized

B

Orange

Equipment terminal

Reversing valve relay energized in heating

NORMAL WHEN

Green

Upper right corner

Panel functioning properly

FLASHING

Table 7.1: LED Description

8.

OPERATION CHECK LIST

Verify that the following controls have been properly configured, installed and adjusted.

1.

High limit

2.

Low limit

3.

Static pressure or barometric bypass damper

4.

All thermostats low setpoint at 68°F (20°C) and high setpoint at 76°F (24°C)

5.

Tag all wiring and system components to correspond to the zone they serve

6.

If HVAC unit incorporates an economizer, it is important that it be checked for proper
operation and that the minimum positioning stop be set.

7.

If the HVAC unit has an economizer that is not equipped with a relief damper, it may be
necessary to relink the return air damper so that it will always remain thirty percent (30%)
open, otherwise the bypass damper system may not perform properly.

SlimZone Classic

11