To Test Thermostat
WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS
VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL
DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.
CAUTION: DO NOT SWITCH SYSTEM TO A/C OR LEAVE IN A/C MODE IF
THE TEMPERATURE IS BELOW 50°F (10°C). THIS CAN
DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PER-
SONAL INJURY.
1. Place the HEAT-OFF-A/C switch into the A/C
position. The
will be displayed.
2. Press the
button until the temperature
setting is at least 3 degrees below the room
temperature. The air conditioning system
should turn on within a few seconds.
NOTE: ONCE THE THERMOSTAT TURNS OFF WHEN IN THE A/C MODE,
A BUILT IN 5-MINUTE DELAY PREVENTS THE SYSTEM FROM
TURNING ON AGAIN. THIS PROTECTS THE COMPRESSOR. NO
ADDITIONAL TIME DELAY RELAY IS REQUIRED. TO OVERRIDE THE
5-MINUTE DELAY FOR INSTALLATION, PRESS THE RESET BUTTON.
3. Put the HEAT-OFF-A/C switch into the OFF
position. The air conditioning system should
turn off.
4. Put the HEAT-OFF-A/C switch into the HEAT
position. The will be displayed.
5. Press the
button until the temperature
setting is at least 3 degrees above room
temperature. The heating system should turn on. The fan may
not turn on immediately, depending on the fan delay built into
the furnace.
NOTE: If HP is selected, the heat will not come on until the 5 minute
short cycle protection has expired.
6. Put the HEAT-OFF-A/C switch into the OFF
position. The heating system should turn off.
The fan may continue to run for a short
period of time.
7. Put the AUTO
ON switch into the ON
position. The blower fan should turn on.
The display will show a
.
8. Put the AUTO
ON switch into the AUTO
position. The blower fan should turn off.
a/c
off
heat
a/c
off
heat
a/c
off
heat
a/c
off
heat
on
auto
on
auto
!