beautypg.com

Prestige series - edge-lit led exit series, Self powered models, Maintenance – Emergi-Lite Prestige Economizer Series - Recessed ceiling-mount User Manual

Page 2

background image

Prestige Series - Edge-Lit LED Exit Series

Emergi-Lite

Tel: (888) 552-6467

Fax: (800) 316-4515

www.emergi-lite.com

04/11 750.1541 Rev. A

2/2

7. Compress the retention springs (Figures 4) and pass them through

the slots on the back box (1) (see figure 2) and push the trim plate
assembly into the back box. Align to be flush with the back box or
with the ceiling.

8. Plug battery (self powered models only).

Self Powered models

Manual testing

Press test switch (see figure 5). Legend will flicker then will remain lit. On
release, external green LED will illuminate, and automatic charger will
restore battery to full charge.

Maintenance

None required. Models equipped with batteries: if AC supply is to be dis-
connected for 2 months or more, the battery must be disconnected (Self-
Powered Models only).

Note — For safety reasons Nickel Cadmium batteries are shipped dis-
charged. The unites may require 10 minutes of connection to AC supply
before start-up test procedure, and two to seven days to reach full
charge.

Figure 3

(Regular models)

Blue - DC

Red + DC

Purple AC

White neutral

Back box

Figure 5

AC Pilot light / Test switch

Trim plate

Figure 4