Emergi-Lite HZM Series User Manual
Important safeguards, Read and follow all safety instructions, Save these
Emergi-Lite
Tel: (888) 552-6467 ext. 547 or 255
Fax: (888) 867-1565
www.emergi-lite.com
03/11 750.0299 Rev. C
1/2
HZM Series
HZM Series
This equipment is rated for Class 1, Division 2, Groups A, B, C and D
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not let power supply cords touch hot surfaces.
2. Do not mount near gas or electric heaters.
3. Use caution when handling batteries. Avoid possible shorting.
4. Equipment should be mounted in locations and at heights where it
will not readily be subjected to tampering by unauthorized personnel.
5. The use of accessory equipment not recommended by the manufac-
turer may cause an unsafe condition.
6. Caution: If optional Halogen cycle lamp(s), symbol (H—), are used in
this equipment, to avoid shattering: do not operate lamp in excess of
rated voltage, protect lamp against abrasion and scratches and
against liquids when lamp is operating, dispose of lamp with care.
7. Halogen cycle lamps operate at high temperatures. Do not store or
place flammable materials near lamp.
8. Do not use this equipment for other than intended use.
9. All servicing should be performed by qualified service personnel.
SAVE THESE
INSTRUCTIONS
Installation Instructions
1. The unit is to be installed with wiring methods in accordance with the
requirements of NEC Article, 500 and 501.
2. Turn off AC power.
3. Route AC circuit wires to electrical box and leave 12” of wire length.
4. Remove four screw on door. Open door by lifting it away from hous-
ing.
5. Securely mount unit in place. Connect AC supply wiring to unit as fol-
lows (see fig. 2):
For 120 VAC operation — Black to 120 VAC, white to neutral. Insu-
late unused wire.
For 277 VAC operation — Orange to 277 VAC, white to neutral.
Insulate unused wire.
6. Extend DC wiring for remote fixtures (if required) to unit. Wiring must
comply with NEC articles 700, 720 and 501-4. Do not exceed rated
wattage of unit, integral and remote lampheads combined.
7. Connect two white lamp wires to black wires from circuit board with
wirenuts provided (see fig. 2). Note: lamp wires are not polarized.
Part List
1. Housing
2. Door
3. Screw (4)
Figure 2
White
120 Black
277 Orange
AC Input
Test
To DC lamps
Battery
Black
White
Black
White
switch
+ –
Figure 1