Teledyne 7120 - NDIR analyzer User Manual
Page 15

Photometric Analyzer
Installation 2
2-7
Teledyne Analytical Instruments
2
0.2
7.2
3
0.3
8.8
4
0.4
10.4
5
0.5
12.0
6
0.6
13.6
7
0.7
15.2
8
0.8
16.8
9
0.9
18.4
10
1.0
20.0
To provide an indication of the range, the Range ID analog outputs are
used. They generate a steady preset voltage (or current when using the
current outputs) to represent a particular range. Table 2-4 gives the range ID
output for each analysis range.
Table 2-4: Analog Range ID Output—Example
Range Voltage (V) Current (mA) Application
Range 1 0.25
8 90-100% CO/N
2
Range 2 0.50
12 95-100% CO/N
2
Range 3 0.75
16 0-100% CO/N
2
Range 4 (Cal) 1.00
20 98-100% CO
2
/N
2
2.3.3.2
Alarm Relays
The nine alarm-circuit connector pins connect to the internal alarm relay
contacts. Each set of three pins provides one set of Form C relay contacts.
Each relay has both normally open and normally closed contact connections.
The contact connections are shown in Figure 2-4. They are capable of
switching up to 3 amperes at 250 V ac into a resistive load. The connectors
are:
Threshold Alarm 1:
• Can be configured as high (actuates when concen-
tration is above threshold), or low (actuates when
concentration is below threshold).
• Can be configured as failsafe or nonfailsafe.
• Can be configured as latching or nonlatching.
• Can be configured out (defeated).
Threshold Alarm 2:
• Can be configured as high (actuates when concen-
tration is above threshold), or low (actuates when