beautypg.com

Teledyne 3350 - Microprocessor based control room monitor for personnel safety User Manual

Page 23

background image

3-7

Alarm Oxygen Monitor

Installation 3

Teledyne Analytical Instruments

Each status output is followed by a carriage return and line feed.

The RS-232 protocol allows some flexibility in its implementation.

Table 3-2 lists certain RS-232 values that are required by the 3350 imple-
mentation.

Table 3-2: Required RS-232 Options

Parameter

Setting

Baud

2400

Byte

8 bits

Parity

none

Stop Bits

1

Message Interval

2 seconds

Alarm Relays must not be connected to any voltage
source greater than 130VAC. Minimum recommended
wire is 16 AWG with 300 VAC insulation

3.5.5 Alarm Relays

The three alarm-circuit connectors are screw terminals for making

connections to internal alarm relay contacts. There is one set of contacts for
each of 3 different types of alarm. Alarm 1 (CAUTION), Alarm 2 (DAN-
GER), and Cell Fail. Contacts are Form C, with normally open and nor-
mally closed contact connections capable of switching up to 3 ampere at 130
VAC into a resistive load (3A for 30 VDC) maximum.

The alarm relay circuits are designed for failsafe operation, meaning the

relays are energized during normal operation. If power fails the relays de-
energize (alarms activated). Alarms are also available factory configured for
non-failsafe operation which would extend the life of the battery standby
power if applicable.

The contact connections are indicated diagrammatically on the rear

panel as Normally Closed, Common, and Normally Open. Figure 3-5
explains how these act in failsafe operation.

Figure 3-5: Contact ID for FAILSAFE Relay Operation